{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Q22425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Q22425","canonicalUrl":"https://aoctrl.com/schneider/A9Q22425","factsUrl":"https://aoctrl.com/api/mcp/products/A9Q22425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 4P, 25 A, 100 mA, Type A, instantaneous, voltage independent, clip-on DIN rail.","salesMarkdown":"The A9Q22425 is an Acti9 Vigi iC60 add-on residual current device (RCD) — a 4-pole, 25 A, 100 mA, Type A block that plugs directly onto the outgoing side of a compatible iC60 MCB. The 54 mm width (6 x 9 mm pitches) and 73.5 mm depth fit the standard Acti9 modular grid, and the bottom tunnel terminals accept up to 25 mm² rigid cable. The 100 mA sensitivity and Type A waveform detection cover sinusoidal AC and pulsating DC earth faults — the standard choice for final circuits with electronics, VFDs, or single-phase rectified loads. The instantaneous trip (no intentional delay) means it clears a fault in under 300 ms, which is the default for socket-outlet and general-purpose circuits where selectivity with an upstream time-delayed RCD is designed in, not assumed. The 25 A rated current matches a 25 A MCB partner; the plug-in mechanical and electrical connection to the MCB means the assembly occupies the same DIN pitch as the breaker alone, saving a module width over a standalone RCD. Pollution degree 3 per IEC 60947-2 means the device is rated for the conductive-dust and occasional-condensation environment of a typical industrial panel — not just clean residential switchgear. The 6 kV impulse withstand voltage (Uimp) and 500 V rated insulation voltage (Ui) give headroom for 230/400 V networks with transient surges. The IP20 (body) and IP40 (modular enclosure) ratings are normal for enclosed distribution boards; no special sealing is needed inside the cabinet. The A9Q22425 carries an Active lifecycle status from Schneider Electric. No cross-reference or substitute is needed — the part is the standard fit.","metaTitle":"A9Q22425 Vigi iC60 4P 25A 100mA Type A RCD, Active","metaDescription":"A9Q22425 Acti9 Vigi iC60 add-on RCD, 4P, 25 A, 100 mA, Type A. Active production. Quoted to order. EN/IEC 61009-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"73.5 mm","Width":"54 mm","Height":"91 mm","Voltage":"230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Product Status":"Active","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Add-on residual current device","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a60acf2cab27a8ae55dc911c47eded59.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9Q22425/vigi-ic60-earth-leakage-addon-block-4p-25a-100ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Q22425/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Q22425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Q22425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}