{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Q51325","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Q51325","canonicalUrl":"https://aoctrl.com/schneider/A9Q51325","factsUrl":"https://aoctrl.com/api/mcp/products/A9Q51325","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60 add-on residual current device, 3P, 25 A, 30 mA, Type A, instantaneous, 400...415 V AC.","salesMarkdown":"The A9Q51325 is an Acti9 Vigi iC60 add-on residual current device (RCD) from Schneider Electric, rated 25 A with a 30 mA sensitivity and Type A earth leakage protection. The 30 mA sensitivity catches earth faults that could be lethal through a person (the standard threshold for personal protection), while the Type A designation means it handles pulsating DC residual currents from rectified loads like electronics or variable-speed drives — not just pure AC sine-wave faults. Mounts via clip-on to DIN rail, occupying 6 x 9 mm pitches (54 mm wide). The tunnel-type terminals on the bottom accept 1...25 mm² rigid cable or 1...16 mm² flexible, with a strip length of 14 mm and a tightening torque of 2 N.m. That's standard for a 25 A outgoing feeder in a domestic or light commercial board. The pollution degree 3 rating (per IEC 60947-2) means it's designed for the conductive dust and condensation you'd find in an industrial panel, not a clean room.","metaTitle":"A9Q51325 Acti9 Vigi iC60 3P 25A 30mA Type A RCD","metaDescription":"A9Q51325 Acti9 Vigi iC60 add-on RCD, 3P, 25 A, 30 mA, Type A, instantaneous. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"73.5 mm","Width":"54 mm","Height":"91 mm","Voltage":"400...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 400...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Product Status":"Active","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Add-on residual current device","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/543338ddf6ea148e7c89a73055bd7221.pdf","sourceUrl":"https://www.se.com/id/en/product/A9Q51325/addon-residual-current-device-acti9-vigi-ic60-3p-25a-a-type-instantaneous-30ma-400-415vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Q51325/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Q51325","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Q51325 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}