{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Q54425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Q54425","canonicalUrl":"https://aoctrl.com/schneider/A9Q54425","factsUrl":"https://aoctrl.com/api/mcp/products/A9Q54425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 4P, 25 A, 300 mA, Type A, instantaneous, 230...415 V AC, clip-on DIN rail.","salesMarkdown":"It provides earth-leakage protection for the outgoing circuit, rated at 25 A with 300 mA sensitivity, Type A (pulsating DC and sinusoidal AC fault detection). The unit is voltage-independent — it trips on residual current alone, no auxiliary supply needed. Four poles (4P) cover three-phase plus neutral circuits on 230...415 V AC networks at 50/60 Hz. The instantaneous trip characteristic means no intentional delay — it clears a ground fault as fast as the sensing circuit allows, which matters for coordination with downstream RCDs in a distribution board. Clip-on mounting onto DIN rail. The unit occupies 6 x 9 mm pitches (54 mm width) and sits 73.5 mm deep by 91 mm tall — standard for the Acti9 modular range. Bottom tunnel terminals accept 1...25 mm² rigid or 1...16 mm² flexible conductors; strip length 14 mm, tighten to 2 N·m. Comb busbar compatible from the bottom. IP20 on the terminals, IP40 on the modular enclosure. Pollution degree 3 per IEC 60947-2 — suitable for conventional industrial panels where conductive dust or humidity is controlled but not eliminated. Rated insulation voltage 500 V AC; impulse withstand 6 kV. 8/20 µs surge withstand at 250 A per IEC 61009-1. Storage temperature -40 to 85 °C; operating ambient -25 to 60 °C.","metaTitle":"Schneider Electric A9Q54425 Acti9 Vigi iC60, 4P 25A 300mA Ty","metaDescription":"Schneider Electric A9Q54425 Acti9 Vigi iC60 add-on RCD, 4P, 25 A, 300 mA Type A, instantaneous. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73.5 mm","Range":"Acti9","Width":"54 mm","Height":"91 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"6","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"2 N.m bottom","[In] rated current":"25 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...25 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"Plug in","Earth leakage protection type":"Type A","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"Bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2381411c55a9985e6c158645cc342764.pdf","sourceUrl":"https://www.se.com/id/en/product/A9Q54425/addon-residual-current-device-acti9-vigi-ic60-4p-25a-a-type-instantaneous-300ma-230-415vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Q54425/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of A9Q54425?","answer":"The A9Q54425 has a depth of 73.5 mm."},{"question":"What is the A9Q54425's rated current and earth-leakage sensitivity?","answer":"Rated at 25 A with 300 mA Type A earth-leakage protection, instantaneous trip."},{"question":"Where can I buy A9Q54425 and get current pricing?","answer":"The A9Q54425 is available to order against an RFQ through independent distribution; pricing and stock are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Q54425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Q54425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}