{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9R11263","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9R11263","canonicalUrl":"https://aoctrl.com/schneider/A9R11263","factsUrl":"https://aoctrl.com/api/mcp/products/A9R11263","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iID RCCB, A9R11263, 63 A, 30 mA, 2P, Type AC, DIN rail.","salesMarkdown":"The Schneider Electric A9R11263 is a 2-pole Acti9 iID residual current circuit breaker (RCCB) rated for 63 A continuous load with a 30 mA earth-leakage sensitivity. The 30 mA trip threshold is the standard for personal shock protection in residential and commercial final circuits — it clears a fault before the heart's vulnerable fibrillation window. The 63 A [In] means it passes the full current of a typical main switch or large cooker circuit; the 30 mA sensitivity (Type AC) catches sinusoidal AC leakage only, not pulsed DC or smooth DC faults. If the downstream load includes VFDs, LED drivers, or switching power supplies that generate non-sinusoidal leakage, a Type A or Type B RCCB is needed instead. Breaking and making capacity is rated at Idm 1500 A and Im 1500 A — that is the fault current this RCCB can safely interrupt under the residual-current and overcurrent conditions defined in EN/IEC 61008-1. The 250 A surge current rating (8/20 µs impulse) confirms it withstands lightning-induced or switching transients without nuisance tripping. Insulation voltage is 500 V AC, so it is suitable for 400 V three-phase systems when used on a single-pole leg (phase-to-neutral). Terminals accept 1...35 mm² rigid or 1...25 mm² flexible cable; strip length 14 mm, tighten to 3.5 N·m. The toggle actuator provides a clear contact-position indicator, and the enclosure carries a padlocking provision for lockout/tagout. IP20 on the body, IP40 inside a modular enclosure — keep the panel door closed during washdown.","metaTitle":"Schneider Electric A9R11263 Acti9 iID RCCB, 63A, 30mA, 2P","metaDescription":"Schneider Electric A9R11263 Acti9 iID RCCB, 63A rated, 30mA sensitivity, 2P, Type AC, DIN rail mount. EN/IEC 61008-1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 61008-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iID","Mounting mode":"Clip-on","Surge current":"250 A","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Device short name":"iID","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"63 A","Electrical durability":"AC-1: 15000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 1500 A Im 1500 A","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV","Rated conditional short-circuit current":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9R11263/acti-9-iid-rccb-2p-63a-30ma-type-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9R11263/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of A9R11263?","answer":"The depth is 73.5 mm, which fits standard shallow enclosures. Overall dimensions are 91 mm height × 36 mm width (4 x 9 mm pitches)."},{"question":"What standard does A9R11263 comply with?","answer":"Complies with EN/IEC 61008-1 for residual current operated circuit breakers without integral overcurrent protection."},{"question":"Where can I buy A9R11263?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9R11263","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9R11263 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}