{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9R22291","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9R22291","canonicalUrl":"https://aoctrl.com/schneider/A9R22291","factsUrl":"https://aoctrl.com/api/mcp/products/A9R22291","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iID, residual current circuit breaker (RCCB), 2P, 100 A, 100 mA sensitivity, Type A, 230/240 V AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9R22291 is an Acti9 iID residual current circuit breaker (RCCB) — a voltage-independent, instantaneous-trip device sized for 100 A at 230/240 V AC, 50/60 Hz, with 100 mA earth-leakage sensitivity and Type A protection class. The 100 mA sensitivity means it is specified for circuits where a lower 30 mA threshold would cause nuisance tripping from leakage in long cable runs or equipment with natural earth-leakage current — common in sub-distribution, industrial socket-outlet circuits, or fixed equipment. Type A detection covers sinusoidal AC and pulsating DC residual currents up to 100 mA, which covers most modern electronic loads with half-wave rectification. ## Integration & termination Mounts on DIN rail via clip-on mechanism. Terminals accept 1–35 mm² rigid or 1–25 mm² flexible conductors top or bottom; strip length 14 mm, tightening torque 3.5 N.m. IP20 body, IP40 inside a modular enclosure — standard for distribution board installation, not washdown. Locking provision via padlocking device. Dimensions: 36 mm wide, 96 mm high, 69 mm deep, with 44 mm embedding depth behind the panel. ## Electrical ratings & standards Rated insulation voltage 500 V AC; operational voltage 230/240 V AC. Breaking and making capacity: Idm 1500 A, Im 1500 A. Electrical durability 15,000 cycles (AC-1), mechanical durability 20,000 cycles. Pollution degree 3. Withstands 8/20 µs impulse current of 250 A per EN/IEC 61008-1. Storage temperature range -40 to 85 °C. Complies with IEC 61008-2-1 and AS/NZS 61008.1.","metaTitle":"Schneider Electric A9R22291 Acti9 iID RCCB, 100 A, 30 mA, Ty","metaDescription":"Schneider Electric A9R22291 Acti9 iID RCCB, 2-pole, 100 A rated current, 100 mA sensitivity, Type A, 230/240 V AC. IEC 61008-2-1. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"69 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"96 mm","Standards":"IEC 61008-2-1 AS/NZS 61008.1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iID","Mounting mode":"Clip-on","Quality labels":"RCM VDE","Embedding depth":"44 mm","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Device short name":"iID","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"100 A","Electrical durability":"AC-1: 15000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 1500 A Im 1500 A","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV","Rated conditional short-circuit current":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/uk/en/product/A9R22291/residual-current-circuit-breaker-rccb-acti9-iid-2p-100a-a-type-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9R22291/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9R22291 and how do I get a price?","answer":"The A9R22291 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is A9R22291's listed depth (69 mm) on this component line?","answer":"The A9R22291 has a depth of 69 mm, with an embedding depth of 44 mm behind the panel face."},{"question":"What is A9R22291's listed range (Acti9) on this component line?","answer":"The A9R22291 belongs to the Schneider Acti9 range, specifically the iID series of residual current circuit breakers."},{"question":"What compliance documentation does this brand provide for A9R22291 (RoHS, REACH, UL, IEC)?","answer":"The A9R22291 carries RCM and VDE quality labels and complies with IEC 61008-2-1 and AS/NZS 61008.1 standards. The evidence does not list RoHS, REACH, or UL documentation specifically for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9R22291","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9R22291 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}