{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9R54225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9R54225","canonicalUrl":"https://aoctrl.com/schneider/A9R54225","factsUrl":"https://aoctrl.com/api/mcp/products/A9R54225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iID, residual current circuit breaker (RCCB), 2P, 25 A, 300 mA Type A, 220-240 V AC, voltage-independent trip, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9R54225 is an Acti9 iID residual current circuit breaker (RCCB) — 2 poles, rated 25 A continuous, with 300 mA earth-leakage sensitivity. It's Type A, meaning it catches sinusoidal AC faults plus pulsating DC residual currents up to 6 mA smooth DC, which covers most modern electronics and variable-speed drives on the line. The trip is voltage-independent, so it clears a ground fault even if the supply neutral is lost — a real advantage in older or poorly grounded installations where an electronic RCCB might stay closed on a fault. Rated operational voltage is 220-240 V AC, 50/60 Hz. That's standard single-phase or split-phase line voltage across most of Europe, Asia, and the Middle East. The 25 A current rating suits sub-main or feeder circuits feeding a group of socket outlets, lighting, or small HVAC loads — not a single high-draw appliance. Breaking capacity is 1500 A (Idm/Im) per EN/IEC 61008-1, which is typical for a domestic or light-commercial RCCB; it's not designed for high-fault industrial panels where SCCR above 10 kA is common. Mechanical durability is 20000 cycles, electrical durability 15000 cycles at AC-1 resistive load. Clip-on mount to DIN rail, 36 mm wide (2 module pitches at 9 mm each). Neutral is on the left. Terminals accept 1-35 mm² rigid or 1-25 mm² flexible (with or without ferrule). Tightening torque 3.5 N.m top or bottom. Wire strip length 14 mm. Padlocking provision for lockout/tagout. Standard 73.5 mm depth — fits any standard distribution board without depth clearance issues.","metaTitle":"Schneider Electric A9R54225 Acti9 iID RCCB, 25 A, 300 mA, Ty","metaDescription":"Schneider Electric A9R54225 Acti9 iID 2P RCCB, 25 A rated current, 300 mA Type A earth-leakage protection, 220-240 V AC, voltage-independent trip. Current production, sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 61008-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iID","Mounting mode":"Clip-on","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Device short name":"iID","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"25 A","Electrical durability":"AC-1: 15000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 1500 A Im 1500 A","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV","Rated conditional short-circuit current":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/id/en/product/A9R54225/acti9-iid-rccb-2p-25a-300ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9R54225/alternatives.json"},"ai":{"faq":[{"question":"What is A9R54225's listed range (Acti9) on this component line?","answer":"It belongs to the Schneider Acti9 range, specifically the iID sub-family of residual current circuit breakers. Acti9 is Schneider's modular DIN-rail system for final distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9R54225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9R54225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}