{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9S70680","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9S70680","canonicalUrl":"https://aoctrl.com/schneider/A9S70680","factsUrl":"https://aoctrl.com/api/mcp/products/A9S70680","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iSW-NA, switch disconnector, 1P+N, 80 A, 230/240 V AC, clip-on DIN rail, EN/IEC 60947-3.","salesMarkdown":"The Schneider Electric A9S70680 is a switch disconnector from the Acti9 iSW-NA series, rated 80 A at 230/240 V AC in utilisation category AC-22A per EN/IEC 60947-3. That AC-22A rating means it is designed for switching mixed resistive and inductive loads, including motor loads up to the rated current, with the isolation function certified — the contact position indicator and positive break confirm the circuit is physically open for safe maintenance. It occupies a 36 mm width (4 x 9 mm pitches) on a DIN rail, clip-on mounting, with a depth of 74 mm and height of 85 mm. The 1P+N configuration places the neutral on the left, switching both phase and neutral. ## Electrical performance and fault handling Rated insulation voltage (Ui) is 500 V AC, with an impulse withstand voltage (Uimp) of 6 kV — figures that confirm it can handle the voltage transients typical in industrial panels. The short-time withstand current (Icw) is 1.2 kA for 1 second, and the short-circuit making capacity (Icm) is 5 kA when used alone as a switch-disconnector. These ratings mean the device can close onto a fault and hold through a downstream short without welding its contacts, provided the upstream protection clears within the 1-second window. Electrical durability is rated at 15,000 cycles under load (AC-22A), mechanical durability at 20,000 cycles. The device is tropicalised (class 2) and operates from -35 °C to 70 °C ambient, with storage from -40 °C to 85 °C. Clip-on DIN rail mounting with a 36 mm footprint — fits standard 35 mm DIN rails in any enclosure. The IP20 finger-safe protection is typical for panel-mounted switchgear; no special sealing required inside the cabinet. The white colour and local ON/OFF indication help with visual identification during commissioning and troubleshooting. Compliant with EN 60947-3 and IEC 60947-3, with suitability for isolation confirmed per those standards. The pollution degree 3 rating and tropicalisation class 2 indicate it is designed for long-term reliability in demanding environments — no special derating needed for typical industrial panel conditions.","metaTitle":"Schneider Electric A9S70680 Acti9 iSW-NA Switch Disconnector","metaDescription":"Schneider Electric A9S70680 Acti9 iSW-NA switch disconnector, 80 A rated, 1P+N, EN/IEC 60947-3. Isolation rated, clip-on DIN rail. Current lifecycle: active production. Quoted to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN 60947-3 IEC 60947-3","9 Mm Pitches":"4","Control type":"Toggle Remote tripping","Product name":"Acti9 iSW-NA","Mounting mode":"Clip-on","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60947-3","Device short name":"iSW-NA","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening Torque":"3.5 N.m","Device application":"Isolation Control","Utilisation category":"AC-22A conforming to EN/IEC 60947-3","Electrical durability":"15000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals (top or bottom) 1 cable(s) 1...25 mm² flexible with cable end Tunnel type terminals (top or bottom) 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminals (top or bottom) 1 cable(s) 1...35 mm² rigid without cable end","IP degree of protection":"IP20","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to EN/IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-3","[Ie] rated operational current":"80 A at 230/240 V AC 50/60 Hz","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-3","[Icw] rated short-time withstand current":"1.2 kA during 1 s","[Icm] rated short-circuit making capacity":"5 kA switch-disconnector alone","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/64706a1a3fc7ddf3a93ef361455ff449.pdf","sourceUrl":"https://www.se.com/za/en/product/A9S70680/switchdisconnector-iswna-1p-+-n-80-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9S70680/alternatives.json"},"ai":{"faq":[{"question":"What is the A9S70680 used for?","answer":"The A9S70680 is a switch disconnector rated 80 A at 230/240 V AC, utilisation category AC-22A per EN/IEC 60947-3. It is used for isolation and control of resistive and mixed loads in industrial panels, mounted on a DIN rail."},{"question":"What are the key ratings of the A9S70680?","answer":"Rated operational current 80 A at 230/240 V AC, rated insulation voltage 500 V AC, impulse withstand 6 kV, short-time withstand 1.2 kA for 1 s, short-circuit making capacity 5 kA. Electrical durability 15,000 cycles, mechanical 20,000 cycles."},{"question":"Where can I buy the A9S70680?","answer":"The A9S70680 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9S70680","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9S70680 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}