{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TAA2240","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TAA2240","canonicalUrl":"https://aoctrl.com/schneider/A9TAA2240","factsUrl":"https://aoctrl.com/api/mcp/products/A9TAA2240","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 ARC iC60, active arc fault detection add-on block, 2P, 40 A, 230 V AC, clip-on DIN rail, white (RAL 9003).","salesMarkdown":"The Schneider Electric A9TAA2240 is an Acti9 ARC iC60 active arc fault detection add-on block — a 2-pole, 40 A device that clips onto the side of an iC60 MCB to add series arc-fault protection per EN/IEC 62606. The 73 mm depth and 54 mm width keep it within the standard Acti9 footprint, so it swaps in without re-spacing the rail. It trips the MCB when the arc energy exceeds the threshold defined in EN/IEC 62606, which covers both series and parallel arcs. The 275 V ±5 V trip threshold for overvoltage detection means it catches a sustained line-to-neutral swell before the arc reaches full fault current — a layer of protection a standard MCB alone doesn't provide. Accuracy on power measurement is ±5 %, good enough for energy logging but not precision metering. Electrical durability is rated at 10,000 cycles under load at 230 V AC per IEC 62606; mechanical durability is 20,000 cycles. That's the standard endurance for a residential-grade AFDD — it's not a motor-starting switch, but it's well matched to the switching frequency of a final-distribution board. Clip-on mounting to the iC60 MCB means the assembly is one DIN-rail unit — no extra wiring between the block and the breaker beyond the screw connection. The tunnel terminals accept 1–10 mm² flexible or 1–16 mm² rigid, with a wire-strip length of 14 mm and a tightening torque of 2 N·m. IP20 rated, so it's for indoor panel use only; the tropicalisation rating (severity B, 28 days per IEC 60068-2-30) covers high-humidity environments like coastal or unconditioned electrical rooms. It communicates event data — overvoltage, earth leakage, overload, and arc fault diagnostics — to EcoStruxure Panel Server concentrators (Advanced, Entry, or Universal) for remote monitoring. The local LED signals ON, OFF, fault trip, and arc fault diagnostic, so a field tech can read the last trip cause without a tool.","metaTitle":"Schneider Electric A9TAA2240 Acti9 ARC iC60, 40 A, 2P, Activ","metaDescription":"Schneider Electric A9TAA2240 Acti9 ARC iC60 active arc fault detection add-on block. 40 A, 2P, 230 V AC, clip-on DIN rail. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White (RAL 9003)","Depth":"73 mm","Width":"54 mm","Height":"91 mm","Voltage":"230 V AC 50 Hz conforming to IEC 62606","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","IP Rating":"IP20","Product Status":"Active","Pollution Degree":"2 conforming to IEC 62606","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"400 V AC 50 Hz","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Electrical Life Cycles":"10000 cycles 230 V AC conforming to IEC 62606","Mechanical Life Cycles":"20000 cycles","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$388.31","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f16c382736f26781686dd24ced5897a7.pdf","sourceUrl":"https://www.se.com/ae/en/product/A9TAA2240/active-arc-fault-detection-addon-block-acti9-active-arc-ic60-2p-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TAA2240/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TAA2240","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TAA2240 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}