{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TAB1225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TAB1225","canonicalUrl":"https://aoctrl.com/schneider/A9TAB1225","factsUrl":"https://aoctrl.com/api/mcp/products/A9TAB1225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 ARC iC60, arc fault detection add-on block, 2 poles, 25 A rated current, 230 V AC, clip-on DIN rail mount.","salesMarkdown":"## Arc fault detection add-on block for the iC60 range The Schneider Electric A9TAB1225 is an Acti9 ARC iC60 arc fault detection add-on block, 2-pole, rated 25 A at 230 V AC. It clips onto the outgoer side of an iC60 MCB to add series arc fault protection per EN/IEC 62606. The 25 A rating matches the branch circuit it protects — sized for the load, not the bus. The 2-pole form factor (2P) switches both line and neutral. The 73 mm depth and 54 mm width occupy two 9 mm DIN pitches — standard for a 2P AFDD add-on. IP20 for dry indoor panel use only. Electrical durability is 10,000 cycles at 230 V AC per IEC 62606; mechanical durability is 20,000 cycles. The local signalling includes ON, OFF, and a fault-trip LED with arc fault diagnostic — useful for commissioning and troubleshooting without a meter. Tropicalisation severity B per IEC 60068-2-30 (28-day damp heat cycling) and 95% RH at 55 °C mean it holds up in non-conditioned electrical rooms in humid climates. Pollution degree 2 per IEC 62606 covers normal industrial environments with only non-conductive contamination.","metaTitle":"Schneider Electric A9TAB1225 Acti9 ARC iC60, 25A, 2P Arc Fau","metaDescription":"Schneider Electric A9TAB1225 Acti9 ARC iC60 arc fault detection add-on block, 2P, 25A, 230V AC. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Width":"54 mm","title":"A9TAB1225","Colour":"White (RAL 9003)","Height":"91 mm","Standards":"EN/IEC 62606","description":"Arc fault detection add-on block, Acti9 ARC iC60, 2P, 25A","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 ARC iC60","Mounting mode":"Clip-on","Quality labels":"IMQ","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to IEC 62606","Range of product":"Acti9","Device short name":"ARC iC60","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","[In] rated current":"25 A","Overvoltage category":"III","Electrical durability":"10000 cycles 230 V AC conforming to IEC 62606","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminal1...10 mm² flexible Tunnel type terminal1...16 mm² rigid","IP degree of protection":"IP20","Device location in system":"Outgoer","Electrical data recording":"Date and time Maintenance indicators","Product or component type":"Arc fault detection add-on block","Threshold tripping voltage":"275 V for +/- 5 V","Electrical connection to mcb":"By screws","[Ui] rated insulation voltage":"250 V AC 50 Hz","[Ue] rated operational voltage":"230 V AC 50 Hz conforming to IEC 62606","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-25...40 °C","[Uimp] rated impulse withstand voltage":"4 kV conforming to IEC 62606"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$271.89","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7f933faa95267dab7e1b9199db329fb7.pdf","sourceUrl":"https://www.se.com/nl/en/product/A9TAB1225/arc-fault-detection-addon-block-acti9-arc-ic60-2p-25a/"},"ai":{"faq":[{"question":"What is the A9TAB1225 used for?","answer":"It is an arc fault detection add-on block for the Acti9 iC60 MCB range, providing series arc fault protection per EN/IEC 62606 for 2-pole, 25 A, 230 V AC branch circuits."},{"question":"How do I get pricing and availability for A9TAB1225?","answer":"Submit an RFQ; the part is sourced to order through independent distribution with pricing and availability confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for A9TAB1225?","answer":"The part carries IMQ quality label and is designed to EN/IEC 62606. Tropicalisation severity B per IEC 60068-2-30 is documented. Specific RoHS/REACH/UL documentation should be confirmed at order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TAB1225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TAB1225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}