{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TAB1225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TAB1225","canonicalUrl":"https://aoctrl.com/schneider/A9TAB1225","factsUrl":"https://aoctrl.com/api/mcp/products/A9TAB1225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 ARC iC60, arc fault detection add-on block, 2 poles, 25 A rated current, 230 V AC, clip-on DIN rail mount.","salesMarkdown":"## Arc fault detection add-on block for the iC60 range The Schneider Electric A9TAB1225 is an Acti9 ARC iC60 arc fault detection add-on block, 2-pole, rated 25 A at 230 V AC. It clips onto the outgoer side of an iC60 MCB to add series arc fault protection per EN/IEC 62606. The 25 A rating matches the branch circuit it protects — sized for the load, not the bus. The 2-pole form factor (2P) switches both line and neutral. The 73 mm depth and 54 mm width occupy two 9 mm DIN pitches — standard for a 2P AFDD add-on. IP20 for dry indoor panel use only. Electrical durability is 10,000 cycles at 230 V AC per IEC 62606; mechanical durability is 20,000 cycles. The local signalling includes ON, OFF, and a fault-trip LED with arc fault diagnostic — useful for commissioning and troubleshooting without a meter. Tropicalisation severity B per IEC 60068-2-30 (28-day damp heat cycling) and 95% RH at 55 °C mean it holds up in non-conditioned electrical rooms in humid climates. Pollution degree 2 per IEC 62606 covers normal industrial environments with only non-conductive contamination.","metaTitle":"Schneider Electric A9TAB1225 Acti9 ARC iC60, 25A, 2P Arc Fau","metaDescription":"Schneider Electric A9TAB1225 Acti9 ARC iC60 arc fault detection add-on block, 2P, 25A, 230V AC. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White (RAL 9003)","Depth":"73 mm","Width":"54 mm","Height":"91 mm","Voltage":"230 V AC 50 Hz conforming to IEC 62606","IP Rating":"IP20","Product Status":"Active","Pollution Degree":"2 conforming to IEC 62606","Temp Storage Max":"80 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"250 V AC 50 Hz","Temp Operating Max":"40 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...80 °C","Electrical Life Cycles":"10000 cycles 230 V AC conforming to IEC 62606","Mechanical Life Cycles":"20000 cycles","Ambient Air Temperature Operation":"-25...40 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$271.89","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7f933faa95267dab7e1b9199db329fb7.pdf","sourceUrl":"https://www.se.com/nl/en/product/A9TAB1225/arc-fault-detection-addon-block-acti9-arc-ic60-2p-25a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TAB1225/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TAB1225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TAB1225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}