{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TAB2225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TAB2225","canonicalUrl":"https://aoctrl.com/schneider/A9TAB2225","factsUrl":"https://aoctrl.com/api/mcp/products/A9TAB2225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active ARC iC60, active arc fault detection add-on block, 2P, 25 A, 230 V AC, EN/IEC 62606, clip-on DIN rail, white RAL 9003.","salesMarkdown":"The A9TAB2225 is a Schneider Electric Acti9 Active ARC iC60 active arc fault detection add-on block, designed to clip onto the left side of a compatible Acti9 iC60 miniature circuit breaker (MCB). It monitors the downstream circuit for series and parallel arc faults, tripping the host MCB when it detects the characteristic high-frequency noise of an arc, per EN/IEC 62606. This is a 2-pole (2P) unit rated at 25 A, 230 V AC, 50 Hz, intended for outgoer positions in final distribution boards. The 25 A rated current (In) matches the host MCB rating. The 230 V AC operational voltage is standard single-phase final circuit level. Wire connections are tunnel-type terminals accepting 1...10 mm² flexible or 1...16 mm² rigid cable, with a tightening torque of 2 N.m and a strip length of 14 mm. The electrical connection to the MCB is via screws, so the block physically bridges onto the breaker's line-side terminals. ## Deployment context and compliance This block is designed for use in final distribution boards (outgoer location) in commercial and industrial installations where arc fault protection is required by local codes or insurance specifications. It is certified to EN/IEC 62606 (the standard for arc fault detection devices, AFDDs). The pollution degree is 2 (normal, non-conductive pollution only), overvoltage category III (distribution level). It carries the IMQ quality label (Italian mark). The unit is tropicalised to severity B per IEC 60068-2-30 for 28 days, meaning it withstands damp heat cycling. It is compatible with the EcoStruxure Panel Server range (Entry, Advanced, Universal) for data recording and remote monitoring of event logs, maintenance indicators, and date/time-stamped trip events.","metaTitle":"A9TAB2225 Acti9 Active ARC iC60, 25 A, 2P, Active Arc Fault","metaDescription":"A9TAB2225 Acti9 Active ARC iC60 add-on block. 25 A, 2P, 230 V AC, EN/IEC 62606. Active arc fault detection for outgoer circuits. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Width":"54 mm","title":"A9TAB2225","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606","description":"Active arc fault detection add-on block, Acti9 Active ARC iC60, 2P, 25A","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 Active ARC iC60","Mounting mode":"Clip-on","Quality labels":"IMQ","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to IEC 62606","Range of product":"Acti9","Device short name":"ARC iC60","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","[In] rated current":"25 A","Type of measurement":"Voltage Active power Current Power factor","Overvoltage category":"III","Electrical durability":"10000 cycles 230 V AC conforming to IEC 62606","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminal1...10 mm² flexible Tunnel type terminal1...16 mm² rigid","IP degree of protection":"IP20","Device location in system":"Outgoer","Electrical data recording":"Date and time Maintenance indicators","Product or component type":"Active arc fault detection add-on block","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Threshold tripping voltage":"275 V for +/- 5 V","Electrical connection to mcb":"By screws","[Ui] rated insulation voltage":"250 V AC 50 Hz","[Ue] rated operational voltage":"230 V AC 50 Hz conforming to IEC 62606","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-25...40 °C","[Uimp] rated impulse withstand voltage":"4 kV conforming to IEC 62606"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$388.31","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/88644d435d7f958d73eb9db7b882fcf3.pdf","sourceUrl":"https://www.se.com/ae/en/product/A9TAB2225/active-arc-fault-detection-addon-block-acti9-active-arc-ic60-2p-25a/"},"ai":{"faq":[{"question":"What is A9TAB2225's listed depth (73 mm) on this component line?","answer":"The depth is 73 mm. This is the dimension from the DIN rail mounting face to the front of the block, including the screw terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TAB2225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TAB2225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}