{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TAB2240","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TAB2240","canonicalUrl":"https://aoctrl.com/schneider/A9TAB2240","factsUrl":"https://aoctrl.com/api/mcp/products/A9TAB2240","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active ARC iC60, active arc fault detection add-on block, 40 A, 2P, 230 V AC, clip-on DIN rail, EN/IEC 62606.","salesMarkdown":"The Schneider Electric A9TAB2240 is an active arc fault detection add-on block from the Acti9 ARC iC60 range. It clips onto the side of a compatible Acti9 MCB (iC60 series) via the clip-on mounting, adding arc-fault, overvoltage, and earth leakage event management to the outgoing circuit. Rated at 40 A and 2 poles, it operates on a 230 V AC, 50 Hz network and conforms to EN/IEC 62606 — the standard for arc fault detection devices (AFDDs). The 40 A rated current ([In]) sets the maximum continuous load this block can monitor and protect. It is sized for final subcircuits — outgoer position — not incoming mains. The 230 V AC rated operational voltage (Ue) matches standard single-phase residential and light commercial supplies. The threshold tripping voltage of 275 V (+/- 5 V) means it triggers an overvoltage event when line voltage exceeds that level, protecting downstream loads from sustained overvoltage conditions. Accuracy on voltage and current is +/- 2 %, power +/- 5 % — sufficient for energy monitoring and fault diagnostics, not for revenue-grade metering. ## Installation and integration notes Clip-on mounting to the iC60 MCB; the add-on block connects electrically to the MCB via screws. Neutral is on the left. Terminals accept 1 to 10 mm² flexible or 1 to 16 mm² rigid wire. Wire stripping length is 14 mm. The block is IP20 — suitable for dry indoor panels only, not washdown or outdoor locations. Pollution degree 2 (non-conductive pollution only, occasional condensation). Rated for tropicalised environments: severity B per IEC 60068-2-30 for 28 days. Local signalling includes ON/OFF status, fault trip LED, and arc fault diagnostic LED. Carries IMQ quality label. Overvoltage category III. Pollution degree 2. Electrical durability: 10,000 cycles at 230 V AC per IEC 62606; mechanical durability: 20,000 cycles. Compatible with EcoStruxure Panel Server concentrators (Entry, Advanced, Universal) for remote monitoring and data recording.","metaTitle":"Schneider Electric A9TAB2240 Acti9 ARC iC60, 40 A, 2P, Activ","metaDescription":"Schneider Electric A9TAB2240 Acti9 Active ARC iC60 add-on block. 40 A rated current, 2P, EN/IEC 62606. Active arc fault detection, overvoltage & earth leakage. Clip-on DIN rail. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Width":"54 mm","title":"A9TAB2240","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606","description":"Active arc fault detection add-on block, Acti9 Active ARC iC60, 2P, 40A","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 Active ARC iC60","Mounting mode":"Clip-on","Quality labels":"IMQ","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to IEC 62606","Range of product":"Acti9","Device short name":"ARC iC60","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","[In] rated current":"40 A","Type of measurement":"Voltage Active power Current Power factor","Overvoltage category":"III","Electrical durability":"10000 cycles 230 V AC conforming to IEC 62606","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminal1...10 mm² flexible Tunnel type terminal1...16 mm² rigid","IP degree of protection":"IP20","Device location in system":"Outgoer","Electrical data recording":"Date and time Maintenance indicators","Product or component type":"Active arc fault detection add-on block","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Threshold tripping voltage":"275 V for +/- 5 V","Electrical connection to mcb":"By screws","[Ui] rated insulation voltage":"250 V AC 50 Hz","[Ue] rated operational voltage":"230 V AC 50 Hz conforming to IEC 62606","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-25...40 °C","[Uimp] rated impulse withstand voltage":"4 kV conforming to IEC 62606"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$388.31","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1c7c49d182cb275560754078f63a1c30.pdf","sourceUrl":"https://www.se.com/ae/en/product/A9TAB2240/active-arc-fault-detection-addon-block-acti9-active-arc-ic60-2p-40a/"},"ai":{"faq":[{"question":"What is the A9TAB2240 used for?","answer":"It is an active arc fault detection add-on block used to add arc-fault, overvoltage, and earth leakage protection to an Acti9 iC60 MCB in a 230 V AC, 50 Hz final subcircuit. It mounts on DIN rail and is rated at 40 A, 2 poles."},{"question":"What are the key ratings of A9TAB2240?","answer":"Rated current 40 A, poles 2P, rated operational voltage 230 V AC, network frequency 50 Hz, threshold tripping voltage 275 V, overvoltage category III, pollution degree 2, IP20, electrical durability 10,000 cycles, mechanical durability 20,000 cycles."},{"question":"Where can I buy A9TAB2240?","answer":"The A9TAB2240 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider Electric provide for A9TAB2240?","answer":"The A9TAB2240 conforms to EN/IEC 62606 (arc fault detection device standard) and carries the IMQ quality label. It is rated for overvoltage category III and pollution degree 2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TAB2240","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TAB2240 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}