{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TDF3613","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TDF3613","canonicalUrl":"https://aoctrl.com/schneider/A9TDF3613","factsUrl":"https://aoctrl.com/api/mcp/products/A9TDF3613","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40 ARC, A9TDF3613, 1P+N RCBO with arc-fault detection, 13 A rated, C-curve, 6 kA Icn / 10 kA Icu breaking capacity, DIN rail clip-on.","salesMarkdown":"## Arc-fault RCBO for final-circuit protection The 1P+N pole configuration switches the line and monitors the neutral, with the neutral position on the left side of the unit. Breaking capacity is 6 kA Icn per EN/IEC 61009-2-1 and 10 kA Icu per EN/IEC 60947-2 at 230 V AC, placing it in breaking capacity code N. The thermal-magnetic trip unit handles the overcurrent side; the arc-fault electronics detect hazardous arcing patterns and trip the internal mechanism, with a local signalling LED indicating ON, OFF, or fault-trip status. The white (RAL 9003) housing carries IP20 finger protection per IEC 60529, suitable for enclosed distribution boards. The 6 kA Icn is the rated short-circuit capacity per the product standard (EN/IEC 61009-2-1); the 10 kA Icu is the ultimate breaking capacity per the industrial standard (EN/IEC 60947-2), meaning the device can interrupt a 10 kA fault once and remain functional, though it may need replacement after such an event. Limitation class 3 means the device limits the let-through energy (I²t) and peak current during a short-circuit, reducing stress on downstream wiring and connected equipment. This is a practical advantage when coordinating with downstream MCBs or protecting sensitive loads. The arc-fault detection function complies with EN/IEC 62606, the standard for AFDDs. It monitors the waveform for characteristic signatures of series arcs (e.g., a loose connection in a junction box) and parallel arcs (e.g., a damaged cable between phase and neutral). The device trips within the time limits defined by the standard, adding a layer of fire-safety protection that a standard RCBO alone cannot provide. ## Installation and wiring notes Cable entry is from top or bottom, giving flexibility in busbar or cable routing within the distribution board. The device is tropicalised to severity B per IEC 60068-2-30 for 28 days, meaning it withstands cyclic humidity and temperature exposure typical of tropical climates. Total power losses are 3.255 W (2.75 W per pole), which matters for thermal management inside a sealed enclosure with multiple devices ganged together.","metaTitle":"Schneider Electric A9TDF3613 Acti9 iCV40 ARC, 13 A C-Curve,","metaDescription":"Schneider Electric A9TDF3613 Acti9 iCV40 ARC arc-fault detection device. 13 A rated current, C-curve, 6 kA Icn / 10 kA Icu breaking capacity. 1P+N, DIN rail mount. Current producti","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40 ARC","Mounting mode":"Clip-on","Quality labels":"OVE","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 62606","Breaking capacity":"6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iCV40N ARC","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","Total power losses":"3.255 W","[In] rated current":"13 A","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Power losses per pole":"2.75 W","Wire stripping length":"14 mm","Breaking capacity code":"N","Connections - terminals":"Tunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Power losses on neutral":"0.507 W","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Arc fault detection RCBO","Suitability for isolation":"Yes","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC 50 Hz between phase and neutral","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"Idm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...50 °C","[Ics] rated service breaking capacity":"6000 A AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/hk/en/product/A9TDF3613/arc-fault-detection-rcbo-acti9-icv40n-arc-1p+n-13a-c-curve-30ma-type-asi-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TDF3613/alternatives.json"},"ai":{"faq":[{"question":"What standards does A9TDF3613 comply with?","answer":"It complies with EN/IEC 62606 (arc-fault detection device standard), EN/IEC 61009-1, EN/IEC 61009-2-1 (RCBO standard), and EN/IEC 60947-2 (low-voltage switchgear standard)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TDF3613","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TDF3613 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}