{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TDF3616","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TDF3616","canonicalUrl":"https://aoctrl.com/schneider/A9TDF3616","factsUrl":"https://aoctrl.com/api/mcp/products/A9TDF3616","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCV40 ARC RCBO, 1P+N, 16 A, C-curve, 6 kA Icn / 10 kA Icu at 230 V AC, DIN-rail clip-on, white (RAL 9003).","salesMarkdown":"The Schneider Electric A9TDF3616 is an Acti9 iCV40 ARC residual current circuit breaker with overcurrent protection (RCBO), 1P+N, rated 16 A with a C-curve magnetic trip characteristic (5...10 x In). It breaks 6 kA Icn per EN/IEC 61009-2-1 and 10 kA Icu per EN/IEC 60947-2 at 230 V AC, 50 Hz — enough for most residential and light commercial final circuits where fault levels stay under 10 kA. The thermal-magnetic trip unit handles overload and short-circuit; the integrated residual current element adds earth-leakage protection in one 36 mm wide DIN-rail module. The 16 A rated current and C-curve (5–10 x In magnetic trip) suit general-purpose socket circuits, lighting, and small appliance loads where inrush is moderate — think office power outlets or domestic ring mains. The 6 kA Icn is the service breaking capacity for routine faults; the 10 kA Icu is the ultimate breaking capacity for rare high-fault events, giving the installer headroom in selectivity coordination with an upstream 10 kA-rated MCB or fuse. IP20 rated — suitable for enclosed distribution boards only. The toggle control with ON/OFF/fault-trip LED and arc-fault diagnostic signalling gives a quick visual on the circuit state.","metaTitle":"A9TDF3616 Acti9 iCV40 ARC 1P+N 16A C-curve RCBO, 6kA/10kA","metaDescription":"Schneider Electric A9TDF3616 Acti9 iCV40 ARC RCBO, 1P+N, 16 A, C-curve, 6 kA Icn / 10 kA Icu. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iCV40 ARC","Mounting mode":"Clip-on","Quality labels":"IMQ AENOR OVE","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 62606","Breaking capacity":"6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iCV40N ARC","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","Total power losses":"3.408 W","[In] rated current":"16 A","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Power losses per pole":"2.65 W","Wire stripping length":"14 mm","Breaking capacity code":"N","Connections - terminals":"Tunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Power losses on neutral":"0.763 W","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Arc fault detection RCBO","Suitability for isolation":"Yes","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC 50 Hz between phase and neutral","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"Idm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...50 °C","[Ics] rated service breaking capacity":"6000 A AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$323.68","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/hk/en/product/A9TDF3616/arc-fault-detection-rcbo-acti9-icv40n-arc-1p+n-16a-c-curve-30ma-type-asi-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TDF3616/alternatives.json"},"ai":{"faq":[{"question":"What is A9TDF3616's listed range (Acti9) on this component line?","answer":"It belongs to the Acti9 range, Schneider Electric's modular DIN-rail protection and control family for final distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TDF3616","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TDF3616 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}