{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TDFC606","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TDFC606","canonicalUrl":"https://aoctrl.com/schneider/A9TDFC606","factsUrl":"https://aoctrl.com/api/mcp/products/A9TDFC606","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active iCV40 ARC arc-fault detection device, 1P+N, 6 A rated current, curve C, 6 kA Icn / 10 kA Icu, clip-on DIN rail, white (RAL 9003).","salesMarkdown":"The 6 kA Icn is the service breaking capacity per EN/IEC 61009-2-1; the 10 kA Icu per EN/IEC 60947-2 is the ultimate breaking capacity, giving headroom for fault currents up to 10 kA at 230 V AC. The thermal-magnetic trip unit handles overloads via a bimetal strip and short-circuits via a solenoid — no electronics to fail in the trip path. The arc-fault detection adds series arc monitoring per EN/IEC 62606, which means it can distinguish a dangerous arc (loose connection, damaged cable) from normal switching arcs. That's the main value over a standard RCBO: it catches faults a thermal-magnetic alone misses. Accuracy for the measurement functions is ±2 % for voltage and current, ±5 % for power — good enough for energy monitoring and fault logging, not for revenue-grade metering. The local signalling includes an LED for arc-fault diagnostics, so a maintenance tech can tell at a glance whether the trip was from an arc event or a conventional overload/earth leakage. ## Deployment context Cable entry from top and bottom gives flexibility in busbar or wired layouts. The tropicalisation rating — severity B per IEC 60068-2-30 for 28 days — means it handles high-humidity storage and operation, which matters for sites in coastal or tropical climates.","metaTitle":"Schneider Electric A9TDFC606 Acti9 Active iCV40 ARC, 6 A, Cu","metaDescription":"Schneider Electric A9TDFC606 Acti9 Active iCV40 ARC arc-fault detection device. 6 A rated current, curve C, 1P+N, 6 kA Icn / 10 kA Icu. Clip-on DIN rail. Active production. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 Active iCV40 ARC","Mounting mode":"Clip-on","Quality labels":"IMQ AENOR OVE","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 62606","Breaking capacity":"6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iCV40N ARC","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","Total power losses":"3.027 W","[In] rated current":"6 A","Type of measurement":"Voltage Active power Current Power factor","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Power losses per pole":"2.91 W","Wire stripping length":"14 mm","Breaking capacity code":"N","Connections - terminals":"Tunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Power losses on neutral":"0.117 W","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Active arc fault detection RCBO","Suitability for isolation":"Yes","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC 50 Hz between phase and neutral","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"Idm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...50 °C","[Ics] rated service breaking capacity":"6000 A AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$356.51","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9TDFC606/active-arc-fault-detection-rcbo-acti9-active-icv40n-arc-1p+n-6a-c-curve-30ma-type-asi-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TDFC606/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9TDFC606?","answer":"Submit an RFQ through this listing; availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings for A9TDFC606?","answer":"6 A rated current, curve C, 1P+N, 6 kA Icn / 10 kA Icu breaking capacity at 230 V AC, 50 Hz. Complies with EN/IEC 62606, EN/IEC 61009-1, EN/IEC 60947-2, and EN/IEC 61009-2-1."},{"question":"What compliance documentation does Schneider provide for A9TDFC606?","answer":"The device carries IMQ, AENOR, and OVE quality labels. Standards compliance includes EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1 (RCBO), EN/IEC 60947-2 (circuit-breaker), and EN/IEC 61009-2-1 (RCBO functional)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TDFC606","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TDFC606 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}