{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TDFC610","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TDFC610","canonicalUrl":"https://aoctrl.com/schneider/A9TDFC610","factsUrl":"https://aoctrl.com/api/mcp/products/A9TDFC610","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 range, iCV40N ARC RCBO, 1P+N, 10 A, C curve, 6 kA Icn, arc-fault detection, clip-on DIN rail mount.","salesMarkdown":"It packs three protection functions into one DIN-rail unit: arc-fault detection per EN/IEC 62606, earth-leakage protection, and thermal-magnetic overcurrent protection (C curve, 10 A rated). For the panel builder, that means one clip-on device covers arc-fault, ground-fault, and branch-circuit overcurrent — no separate AFCI module needed, saving two DIN spaces. Breaking capacity: 6 kA Icn at 230 V AC per EN/IEC 61009-2-1 (the RCBO standard), and 10 kA Icu per EN/IEC 60947-2 (the MCCB standard). Measurement accuracy: ±2 % on voltage and current, ±5 % on active power and power factor. That's metering-grade — good enough for energy monitoring and load profiling on a branch circuit, not utility-billing accuracy. The device reports these values locally via the arc-fault diagnostic LED and toggle position, not over a bus. Clip-on DIN rail mount, 36 mm wide (4 x 9 mm pitches), 73 mm deep. That 73 mm depth is tight in shallow enclosures — check your gland-plate clearance if the panel is under 80 mm useable depth. Rated for pollution degree 2, overvoltage category III, and tropicalisation severity B per IEC 60068-2-30 (28-day damp-heat cycle). That means it's fine in unconditioned enclosures, humid basements, or outdoors under a weatherproof housing — the 95 % RH at 55 °C limit covers most European and coastal installations. ## Approvals and compliance paperwork Carries IMQ, AENOR, and OVE quality labels — those are Italian, Spanish, and Austrian national marks, respectively. Standards compliance: EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1 and -2-1 (RCBO), and EN/IEC 60947-2 (MCCB supplementary). For the quality-doc controller, that covers the European Low Voltage Directive via CE marking; no separate UL or CSA listing is on the record.","metaTitle":"Schneider Electric A9TDFC610 Acti9 iCV40 ARC RCBO, 10 A, C C","metaDescription":"Schneider A9TDFC610 Acti9 iCV40 ARC RCBO. 10 A rated, C curve, 6 kA Icn / 10 kA Icu. Arc-fault detection per IEC 62606. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 Active iCV40 ARC","Mounting mode":"Clip-on","Quality labels":"IMQ AENOR OVE","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 62606","Breaking capacity":"6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iCV40N ARC","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","Total power losses":"2.906 W","[In] rated current":"10 A","Type of measurement":"Voltage Active power Current Power factor","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Power losses per pole":"2.55 W","Wire stripping length":"14 mm","Breaking capacity code":"N","Connections - terminals":"Tunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Power losses on neutral":"0.355 W","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Active arc fault detection RCBO","Suitability for isolation":"Yes","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC 50 Hz between phase and neutral","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"Idm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...50 °C","[Ics] rated service breaking capacity":"6000 A AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$356.51","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9TDFC610/active-arc-fault-detection-rcbo-acti9-active-icv40n-arc-1p+n-10a-c-curve-30ma-type-asi-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TDFC610/alternatives.json"},"ai":{"faq":[{"question":"What standards does A9TDFC610 comply with?","answer":"EN/IEC 62606 for arc-fault detection, EN/IEC 61009-1 and 61009-2-1 for RCBO construction and testing, and EN/IEC 60947-2 for MCCB-level breaking capacity. Also carries IMQ, AENOR, and OVE quality marks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TDFC610","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TDFC610 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}