{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TDFC613","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TDFC613","canonicalUrl":"https://aoctrl.com/schneider/A9TDFC613","factsUrl":"https://aoctrl.com/api/mcp/products/A9TDFC613","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active iCV40 ARC, A9TDFC613, 13 A rated, 1P+N, Curve C, 6 kA Icn at 230 V AC, 50 Hz, DIN-rail clip-on.","salesMarkdown":"The thermal-magnetic trip handles overloads and short-circuits while the embedded electronics monitor for series and parallel arcs, tripping the circuit before a fire can start. The 13 A rating on a Curve C trip means this unit is sized for general-purpose loads with moderate inrush — think lighting circuits, small appliances, or control transformers in a distribution board. The 10 kA Icu (ultimate breaking capacity per EN/IEC 60947-2) is the one-shot maximum it can interrupt without being destroyed — that's the number for coordination with an upstream breaker. The limitation class 3 means it lets through less energy during a short-circuit than a class 1 or 2 device, which helps protect downstream wiring and loads. The arc-fault detection meets EN/IEC 62606, which is the standard for AFDDs in residential and similar buildings. It measures voltage, current, active power, and power factor (accuracy ±2% for voltage and current, ±5% for power) to distinguish normal arcing (like a motor brush) from dangerous arcing (like a frayed cord). The local signalling includes an ON/OFF toggle, a fault-trip LED, and a dedicated arc-fault diagnostic LED — so when you walk the route and see a solid red instead of green, you know it's an arc event, not just an overload. This is a DIN-rail clip-on device, 91 mm tall and 73 mm deep, with the neutral on the left. The 2 N.m tightening torque and 14 mm wire strip length are standard for Acti9 terminals — spring-cage or screw, same prep. It's rated for pollution degree 2 (normal indoor, non-conductive contamination) and overvoltage category III (distribution level, not the utility transformer side). The 2000 m operating altitude covers most installations below 6500 ft without derating.","metaTitle":"A9TDFC613 Acti9 Active iCV40 ARC 13A 1P+N MCB/RCD, Curve C","metaDescription":"A9TDFC613 Acti9 Active iCV40 ARC arc-fault detection device, 13 A rated, 1P+N, Curve C, 6 kA breaking capacity. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 Active iCV40 ARC","Mounting mode":"Clip-on","Quality labels":"OVE","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 62606","Breaking capacity":"6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iCV40N ARC","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","Total power losses":"3.255 W","[In] rated current":"13 A","Type of measurement":"Voltage Active power Current Power factor","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Power losses per pole":"2.75 W","Wire stripping length":"14 mm","Breaking capacity code":"N","Connections - terminals":"Tunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Power losses on neutral":"0.507 W","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Active arc fault detection RCBO","Suitability for isolation":"Yes","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC 50 Hz between phase and neutral","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"Idm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...50 °C","[Ics] rated service breaking capacity":"6000 A AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/hk/en/product/A9TDFC613/active-arc-fault-detection-rcbo-acti9-active-icv40n-arc-1p+n-13a-c-curve-30ma-type-asi-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TDFC613/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9TDFC613 and what is the lead time?","answer":"A9TDFC613 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest lead time."},{"question":"What is the breaking capacity of A9TDFC613?","answer":"The A9TDFC613 has a 6 kA Icn (service breaking capacity) and a 10 kA Icu (ultimate breaking capacity) at 230 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2 respectively."},{"question":"What standards does A9TDFC613 comply with?","answer":"A9TDFC613 complies with EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1 and 61009-2-1 (RCBO), and EN/IEC 60947-2 (MCB). It carries the OVE quality label."},{"question":"What is the closest alternative to A9TDFC613?","answer":"Within the Acti9 range, the standard iCV40 (without arc-fault detection) is the closest functional alternative if arc detection is not required, but it is not pin-compatible — the A9TDFC613 has the arc diagnostic circuit and additional terminals. For a direct replacement with arc protection, stick with the A9TDFC613."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TDFC613","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TDFC613 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}