{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TDND625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TDND625","canonicalUrl":"https://aoctrl.com/schneider/A9TDND625","factsUrl":"https://aoctrl.com/api/mcp/products/A9TDND625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active iCV40H ARC arc-fault detection device, 1P+N, 25 A, C-curve, 10 kA breaking capacity at 230 V AC, DIN-rail mount.","salesMarkdown":"It is rated 25 A with a C-curve trip characteristic and a breaking capacity of 10000 A Icn at 230 V AC 50 Hz, per EN/IEC 61009-2-1. The integrated arc-fault detection meets EN/IEC 62606, meaning it distinguishes series and parallel arcs from normal load current and trips before a sustained arc can ignite surrounding material. The toggle control provides local signalling: ON, OFF, and a fault-trip LED with arc-fault diagnostic. The 25 A rated current (In) with C-curve means the magnetic trip threshold is 5 to 10 times In — 125 to 250 A instantaneous — sized for motor-starting or transformer inrush on lighting and general-purpose circuits. The limitation class 3 indicates the let-through energy is moderate, so verify coordination with the service entrance breaker. Accuracy for the metering functions (voltage ±2%, current ±2%, power ±5%) is adequate for energy monitoring and fault logging but not for revenue-grade billing. The thermal-magnetic trip unit handles overload and short-circuit; the arc-fault electronics add series and parallel arc detection on top of that. Pollution degree 2 (non-conductive, occasional condensation) per EN/IEC 62606 covers most indoor panels. Operating altitude up to 2000 m, relative humidity 95% at 55 °C, tropicalisation severity B per IEC 60068-2-30 for 28 days — suitable for coastal or high-humidity environments without conformal coating. Electrical durability 20000 cycles at 230 V AC, mechanical 20000 cycles. Neutral is on the left (1P+N configuration).","metaTitle":"Schneider Electric A9TDND625 Acti9 iCV40H ARC, 25 A, 10 kA,","metaDescription":"Schneider Electric A9TDND625 Acti9 Active iCV40H ARC arc-fault detection device. 25 A rated, 10 kA breaking capacity at 230 V AC, C-curve. DIN-rail mount. Available to order; confi","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 Active iCV40 ARC","Mounting mode":"Clip-on","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Earth leakage Overload","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 62606","Targeted country":"India","Breaking capacity":"10000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40H ARC","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","Total power losses":"5.487 W","[In] rated current":"25 A","Type of measurement":"Voltage Active power Current Power factor","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Power losses per pole":"3.5 W","Wire stripping length":"14 mm","Breaking capacity code":"H","Connections - terminals":"Tunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Power losses on neutral":"1.991 W","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Active arc fault detection RCBO","Suitability for isolation":"Yes","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC 50 Hz between phase and neutral","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"Idm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...50 °C","[Ics] rated service breaking capacity":"7500 A AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9TDND625/active-arc-fault-detection-rcbo-acti9-active-icv40h-arc-1p+n-25a-c-curve-30ma-type-asi-10000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TDND625/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9TDND625 and what is the lead time?","answer":"The A9TDND625 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price."},{"question":"What is the breaking capacity of the A9TDND625?","answer":"The breaking capacity is 10000 A Icn at 230 V AC 50 Hz, conforming to EN/IEC 61009-2-1. The H code in the device short name (iCV40H ARC) indicates this higher breaking capacity variant."},{"question":"What standards does the A9TDND625 comply with?","answer":"It complies with EN/IEC 62606 (arc-fault detection devices), EN/IEC 61009-1 (residual current operated circuit-breakers with integral overcurrent protection), and EN/IEC 61009-2-1 (general rules for RCBOs). Pollution degree 2 and overvoltage category III per those standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TDND625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TDND625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}