{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TDND632","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TDND632","canonicalUrl":"https://aoctrl.com/schneider/A9TDND632","factsUrl":"https://aoctrl.com/api/mcp/products/A9TDND632","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active iCV40H ARC RCBO, 32 A rated current, 10 kA breaking capacity, curve C, 1P+N poles, clip-on DIN rail mount, white (RAL 9003).","salesMarkdown":"## Arc-fault detection RCBO for final circuits It occupies a single 36 mm DIN-rail module (4 x 9 mm pitches) and clips directly onto the rail. The 10,000 A Icn breaking capacity at 230 V AC 50 Hz (conforming to EN/IEC 61009-2-1) covers most residential and light commercial fault levels. The 1P+N configuration switches the phase and monitors the neutral, with the neutral position on the left. This unit also includes arc-fault detection (AFDD functionality per EN/IEC 62606), so it responds to series and parallel arcs that a standard thermal-magnetic trip would miss. The trip unit is thermal-magnetic for overcurrent and earth leakage protection, with event management covering earth leakage and overload events. Local signalling shows ON, OFF, fault trip LED, and arc fault diagnostic status on the front face. Accuracy for the measurement functions — voltage, current, active power, power factor — is ±2% for voltage and current, ±5% for power. The device is tropicalised to severity B (28 days, IEC 60068-2-30) and rated for pollution degree 2, with an operating altitude of 2000 m. Relative humidity tolerance is 95% at 55 °C. Clip-on mounting to standard DIN rail; cable entry from top and bottom. The white (RAL 9003) housing matches standard Acti9 panel aesthetics. Standards compliance: EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1 and EN/IEC 61009-2-1 (RCBO). Limitation class 3. Overvoltage category III. Targeted country: India.","metaTitle":"A9TDND632 Acti9 iCV40H ARC RCBO, 32 A, 10 kA, 1P+N","metaDescription":"A9TDND632 Acti9 Active iCV40H ARC RCBO. 32 A rated, 10 kA breaking capacity, curve C, 1P+N. Current production. Sourced to order. Get a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 Active iCV40 ARC","Mounting mode":"Clip-on","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Earth leakage Overload","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 62606","Targeted country":"India","Breaking capacity":"10000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iCV40H ARC","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","Total power losses":"6.333 W","[In] rated current":"32 A","Type of measurement":"Voltage Active power Current Power factor","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Power losses per pole":"4.48 W","Wire stripping length":"14 mm","Breaking capacity code":"H","Connections - terminals":"Tunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Power losses on neutral":"1.852 W","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Active arc fault detection RCBO","Suitability for isolation":"Yes","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC 50 Hz between phase and neutral","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"Idm 3000 A at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...50 °C","[Ics] rated service breaking capacity":"7500 A AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9TDND632/active-arc-fault-detection-rcbo-acti9-active-icv40h-arc-1p+n-32a-c-curve-30ma-type-asi-10000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TDND632/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9TDND632?","answer":"The A9TDND632 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmed at quote time."},{"question":"What are the key ratings for A9TDND632?","answer":"Rated current 32 A, curve C, breaking capacity 10,000 A Icn at 230 V AC 50 Hz, 1P+N poles. Includes arc-fault detection per EN/IEC 62606."},{"question":"What compliance documentation does this brand provide for A9TDND632?","answer":"The A9TDND632 complies with EN/IEC 62606, EN/IEC 61009-1, and EN/IEC 61009-2-1. It is tropicalised per IEC 60068-2-30 severity B. The targeted country is India."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TDND632","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TDND632 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}