{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TPE4610","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TPE4610","canonicalUrl":"https://aoctrl.com/schneider/A9TPE4610","factsUrl":"https://aoctrl.com/api/mcp/products/A9TPE4610","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40 ARC arc fault detection circuit breaker, A9TPE4610, 1P+N, 10 A, C-curve, 6 kA Icn per EN/IEC 60898-1, 10 kA Icu per EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric A9TPE4610 is an Acti9 iC40 ARC arc fault detection circuit breaker (AFDD) — a 1P+N device rated 10 A with a C-curve magnetic trip of 5...10 x In. The arc fault detection electronics monitor the line for series and parallel arc faults, and the local signalling includes a dedicated LED for arc fault diagnostics — so when the breaker trips, you know whether it was an overload/short or an arc event. The 3 kA Icn1 rating at 230 V AC is a lower conditional rating for specific coordination — the 6 kA Icn is the one to use for general branch-circuit protection. The part also complies with EN/IEC 62606, the arc fault detection device standard, so it covers all three: MCB, MCCB, and AFDD requirements in one DIN-rail module. Clip-on mounting to DIN rail, 36 mm wide (4 x 9 mm pitches), 91 mm tall, 73 mm deep. Tunnel terminals accept 1...16 mm² rigid or 1...10 mm² flexible, with a 2 N.m tightening torque and 14 mm strip length. Cable entry from top and bottom, neutral on the left. IP20 finger-safe terminals — fine for enclosed panelboards, not for wet locations. Tropicalisation severity B per IEC 60068-2-30 for 28 days means it handles high-humidity environments without condensation damage.","metaTitle":"Schneider Electric A9TPE4610 Acti9 iC40 ARC, 10 A C-curve AF","metaDescription":"Schneider Electric A9TPE4610 Acti9 iC40 ARC arc fault detection circuit breaker. 10 A rated, C-curve, 1P+N, 6 kA Icn. Current production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2 EN/IEC 62606","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40 ARC","Mounting mode":"Clip-on","Quality labels":"AENOR OVE","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Breaking capacity":"3000 A Icn1 at 230 V AC 50 Hz conforming to EN/IEC 60898-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1","Device short name":"iC40 ARC","Network frequency":"50 Hz","Poles description":"1P + N","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"10 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminal 1...10 mm² flexible Tunnel type terminal 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Device location in system":"Outgoer","Number of protected poles":"1","Product or component type":"Arc fault detection circuit breaker","Suitability for isolation":"Yes","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC","[Ue] rated operational voltage":"230 V AC 50 Hz","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-25...40 °C","[Ics] rated service breaking capacity":"6000 A conforming to EN/IEC 60898-1 7.5 kA conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$256.82","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9TPE4610/arc-fault-detection-circuit-breaker-acti9-ic40n-arc-1p+n-10a-c-curve-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TPE4610/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9TPE4610?","answer":"6 kA Icn at 230 V AC per EN/IEC 60898-1, and 10 kA Icu at 230 V AC per EN/IEC 60947-2. There is also a 3 kA Icn1 rating under the same standards."},{"question":"What standards does the A9TPE4610 comply with?","answer":"It complies with EN/IEC 60898-1 (MCB standard), EN/IEC 60947-2 (MCCB standard), and EN/IEC 62606 (arc fault detection device standard)."},{"question":"Where can I buy A9TPE4610 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TPE4610","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TPE4610 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}