{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TPED610","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TPED610","canonicalUrl":"https://aoctrl.com/schneider/A9TPED610","factsUrl":"https://aoctrl.com/api/mcp/products/A9TPED610","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active ARC iC40N, arc-fault detection circuit breaker, A9TPED610, 1P+N, 10 A, C-curve, 6 kA Icn at 230 V AC.","salesMarkdown":"## Arc-fault MCB for final subcircuits It combines overcurrent protection (thermal-magnetic, C-curve, 10 A rated) with series arc-fault detection per EN/IEC 62606, in a 1P+N (single-pole switched neutral) format. The 6 kA Icn at 230 V AC (EN/IEC 60898-1) and 10 kA Icu (EN/IEC 60947-2) cover the fault-clearing demands of residential and light-commercial final subcircuits. The 6 kA Icn is the service breaking capacity under IEC 60898-1 — adequate for domestic panels with a typical upstream fault level below 6 kA. The 10 kA Icu (IEC 60947-2) is the ultimate breaking capacity for industrial backplanes where higher fault current is possible; the part can interrupt a 10 kA fault once and must then be replaced. Limitation class 3 means it lets through very little let-through energy (I²t) on a short-circuit, protecting downstream wiring and loads. Clip-on mounting to DIN rail (EN 60715). Width is 36 mm (4 x 9 mm pitches). Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; strip length 14 mm, tighten to 2 N·m. Cable entry top and bottom. Neutral position left. IP20 finger-safe terminals. Tropicalisation severity B per IEC 60068-2-30 for 28 days — suitable for humid environments without condensation. ## Arc-fault detection and diagnostics Local signalling: ON/OFF toggle position plus a fault-trip LED and arc-fault diagnostic indicator. Event management covers overvoltage, earth leakage, overload, and series arc faults. Electrical data recording logs date/time and maintenance indicators — useful for post-fault analysis. Measurement accuracy: voltage ±2%, current ±2%, power ±5%.","metaTitle":"Schneider Electric A9TPED610 Acti9 iC40N ARC, 10 A, 1P+N, C-","metaDescription":"Schneider Electric A9TPED610 Acti9 Active ARC iC40N arc-fault MCB. 10 A rated, 1P+N, C-curve, 6 kA Icn. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 60898-1 EN/IEC 60947-2 EN/IEC 62606","Curve code":"C","Cable Entry":"Top and bottom","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 Active ARC iC40","Mounting mode":"Clip-on","Quality labels":"AENOR OVE","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Limitation class":"3","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Breaking capacity":"3000 A Icn1 at 230 V AC 50 Hz conforming to EN/IEC 60898-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1","Device short name":"iC40N ARC","Network frequency":"50 Hz","Poles description":"1P + N","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"10 A","Type of measurement":"Voltage Active power Current Power factor","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminal 1...10 mm² flexible Tunnel type terminal 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Device location in system":"Outgoer","Electrical data recording":"Date and time Maintenance indicators","Number of protected poles":"1","Product or component type":"Active arc fault detection circuit breaker","Suitability for isolation":"Yes","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Contact position indicator":"Yes","Threshold tripping voltage":"275 V for +/- 5 V","Locking options description":"Padlocking device","Product specific application":"Arc fault detection","[Ui] rated insulation voltage":"250 V AC","[Ue] rated operational voltage":"230 V AC 50 Hz","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-25...40 °C","[Ics] rated service breaking capacity":"6000 A conforming to EN/IEC 60898-1 7.5 kA conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$353.05","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/hk/en/product/A9TPED610/active-arc-fault-detection-circuit-breaker-acti9-active-ic40n-arc-1p+n-10a-c-curve-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TPED610/alternatives.json"},"ai":{"faq":[{"question":"What standards does the A9TPED610 comply with?","answer":"It complies with EN/IEC 60898-1 (MCB standard), EN/IEC 60947-2 (industrial circuit-breaker standard), and EN/IEC 62606 (arc-fault detection device standard). Quality labels include AENOR and OVE."},{"question":"Where can I buy the A9TPED610?","answer":"The A9TPED610 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the A9TPED610?","answer":"The service breaking capacity (Icn) is 6 kA at 230 V AC per EN/IEC 60898-1. The ultimate breaking capacity (Icu) is 10 kA at 230 V AC per EN/IEC 60947-2. There is also a 3 kA Icn1 rating under the same standard."},{"question":"What is the closest alternative to A9TPED610 in the Acti9 family?","answer":"The standard Acti9 iC40N (without arc-fault detection) shares the same 1P+N, 10 A, C-curve, 6 kA Icn ratings and the same 36 mm width, but lacks the series arc-fault detection and diagnostic features of the Active ARC variant. For arc-fault protection, the A9TPED610 is the correct choice."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TPED610","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TPED610 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}