{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TYA4225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TYA4225","canonicalUrl":"https://aoctrl.com/schneider/A9TYA4225","factsUrl":"https://aoctrl.com/api/mcp/products/A9TYA4225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 VigiARC iC60, arc fault detection with residual current protection add-on block, A9TYA4225, 25 A, 30 mA, 2P, 230 V AC, DIN rail clip-on.","salesMarkdown":"The A9TYA4225 is an Acti9 VigiARC iC60 add-on block that combines arc fault detection with residual current protection in a single 2-pole module. The 25 A rated current and 230 V AC operational voltage suit it for final circuits supplying socket outlets, lighting, or small appliances in residential or light commercial panels where the standard demands AFDD + RCD in one device. The 30 mA earth-leakage sensitivity is Type A-SI (Super Immunised), meaning it handles pulsed DC fault currents and resists nuisance tripping from high-frequency inverter or LED-driver leakage — a common pain point in modern panels where non-linear loads are present. The arc fault detection follows EN/IEC 62606, so it discriminates between harmless arcs (motor brush noise, switch arcing) and dangerous series/parallel arcs that cause electrical fires. Voltage-independent residual current tripping means the RCD function operates even if the neutral is lost upstream — the trip coil draws its energy from the fault itself, not the supply. Rated insulation voltage is 400 V AC, impulse withstand 4 kV, and pollution degree 2 — standard for a clean indoor distribution board. The 50 Hz network frequency and 2-pole configuration (switched phase + switched neutral, neutral left) match the common single-phase final circuit layout across Europe and many other 50 Hz territories. IP20 finger-safe terminals are fine for enclosed distribution boards; no washdown rating here. ## Field diagnostics and data Local signalling includes ON/OFF position and a fault-trip LED with arc fault diagnostic — the LED distinguishes between arc fault trips and earth-leakage trips, saving a service call to identify the cause. Electrical data recording logs date, time, and maintenance indicators, which helps track recurring faults on a circuit.","metaTitle":"A9TYA4225 Acti9 VigiARC iC60, 25 A, 30 mA, 2P","metaDescription":"A9TYA4225 Acti9 VigiARC iC60 arc fault detection with residual current add-on block. 25 A, 30 mA Type A-SI, 230 V AC, 2P, DIN rail. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White (RAL 9003)","Depth":"73 mm","Width":"54 mm","Height":"91 mm","Voltage":"230 V AC","IP Rating":"IP20","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"400 V AC","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Electrical Life Cycles":"10000 cycles > 25 A 20000 cycles <= 25 A","Mechanical Life Cycles":"20000 cycles","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$329.99","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5b3709b641140d470a38cf1486cc4b6d.pdf","sourceUrl":"https://www.se.com/ae/en/product/A9TYA4225/arc-fault-detection-with-residual-current-protection-addon-block-acti9-vigiarc-ic60-2p-25a-30ma-type-asi/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TYA4225/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TYA4225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TYA4225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}