{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TYAE225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TYAE225","canonicalUrl":"https://aoctrl.com/schneider/A9TYAE225","factsUrl":"https://aoctrl.com/api/mcp/products/A9TYAE225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active VigiARC iC60, arc-fault detection + residual-current add-on block, 2P, 25 A, 30 mA, 230 V AC, clip-on DIN-rail mount.","salesMarkdown":"The Schneider Electric A9TYAE225 is an Active arc-fault detection device with residual-current protection — a combined AFDD + RCD add-on block from the Acti9 VigiARC iC60 range. Rated at 25 A continuous on a 230 V AC network (50 Hz), with an insulation voltage of 400 V AC. The trip threshold for overvoltage is 275 V ±5 V — meaning it catches sustained swells that could start a fire in loose connections or degraded insulation. Built to EN/IEC 62606 (arc-fault detection devices), EN/IEC 61009-1 (RCBOs), and EN/IEC 61009-2-1 (functional). Earth-leakage protection is Type A-SI (Super Immunised), which means it resists nuisance tripping from high-frequency harmonics or transient surges common on inverter-fed circuits or long cable runs. Clip-on mount on standard DIN rail (35 mm), 2-pitch wide (9 mm per pitch). Dimensions: 91 mm high, 54 mm wide, 73 mm deep. Terminals accept 0.2–2.5 mm² solid or stranded wire; strip length 14 mm, tighten to 2 N·m. Pollution degree 2 (normal, non-conductive). Ambient storage range -40 to 85 °C, tropicalised to severity B per IEC 60068-2-30 for 28 days — survives the nacelle or a humid panel room. ## Signalling and diagnostics Local signalling includes ON, OFF, fault-trip LED, and an arc-fault diagnostic indicator. Records date/time of events and maintenance indicators — compatible with EcoStruxure Panel Server (Entry, Advanced, Universal) for remote monitoring. Accuracy for voltage, current, and power is ±2 %; power factor measurement is ±5 %. Electrical durability: 20,000 cycles at ≤25 A, 10,000 cycles above. Mechanical durability: 20,000 cycles.","metaTitle":"Schneider Electric A9TYAE225 Acti9 VigiARC iC60, 25 A 30 mA","metaDescription":"A9TYAE225 Acti9 VigiARC iC60 arc-fault + residual-current add-on block. 25 A, 30 mA, 230 V AC, 2P, DIN-rail. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Width":"54 mm","title":"A9TYAE225","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1","description":"Active arc fault detection with residual current protection add-on block, Acti9 Active VigiARC iC60, 2P, 25A, 30mA, type A-SI","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 Active VigiARC iC60","Mounting mode":"Clip-on","Quality labels":"NF","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Range of product":"Acti9","Device short name":"VigiARC iC60","Network frequency":"50 Hz","Poles description":"2P","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"25 A","Type of measurement":"Voltage Active power Current Power factor","Electrical durability":"10000 cycles > 25 A 20000 cycles <= 25 A","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","IP degree of protection":"IP20 conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Product or component type":"Active arc fault detection with residual current protection add-on block","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Threshold tripping voltage":"275 V for +/- 5 V","[Ui] rated insulation voltage":"400 V AC","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$395.87","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0afe8cf8915d3f5b0fae0234134bc577.pdf","sourceUrl":"https://www.se.com/ae/en/product/A9TYAE225/active-arc-fault-detection-with-residual-current-protection-addon-block-acti9-active-vigiarc-ic60-2p-25a-30ma-type-asi/"},"ai":{"faq":[{"question":"Who supplies A9TYAE225 and how is it quoted for volume purchases?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What are the key ratings on A9TYAE225?","answer":"Rated 25 A continuous, 30 mA earth-leakage sensitivity, 230 V AC operational voltage, 400 V AC insulation voltage, 50 Hz network frequency."},{"question":"What standards does A9TYAE225 comply with?","answer":"Compliant with EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1 (RCBOs), and EN/IEC 61009-2-1 (functional). Earth-leakage protection is Type A-SI (Super Immunised)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TYAE225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TYAE225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}