{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TYB4225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TYB4225","canonicalUrl":"https://aoctrl.com/schneider/A9TYB4225","factsUrl":"https://aoctrl.com/api/mcp/products/A9TYB4225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 VigiARC iC60, arc-fault detection with residual current protection add-on block, 2P, 25 A, 30 mA, 230 V AC, DIN rail.","salesMarkdown":"The 25 A rated current (In) and 30 mA residual sensitivity define the circuit it can protect: a 25 A final subcircuit supplying lighting, socket outlets, or small appliances, with the 30 mA threshold providing personnel protection against indirect contact. The earth-leakage protection is Type A-SI (Super Immunised), meaning it is immune to nuisance tripping from high-frequency leakage currents generated by modern switched-mode power supplies or variable-speed drives — a common pain point in commercial fit-outs. Arc-fault detection conforms to EN/IEC 62606, while the residual current portion meets EN/IEC 61009-1 and EN/IEC 61009-2-1. The device is voltage-independent for residual current tripping, so it still clears an earth fault even if the line voltage collapses — a reliability advantage for circuits where a lost neutral could otherwise mask a fault. Electrical durability is rated at 10,000 cycles above 25 A and 20,000 cycles at or below 25 A; mechanical durability is 20,000 cycles. For a typical residential final circuit switched a few times per week, this translates to decades of service life. The local signalling includes ON, OFF, and fault-trip LED with arc-fault diagnostic, which helps a commissioning engineer identify the cause of a trip without additional test gear.","metaTitle":"Schneider Electric A9TYB4225 Acti9 VigiARC iC60, 25 A, 30 mA","metaDescription":"Schneider Electric A9TYB4225 Acti9 VigiARC iC60 arc-fault detection device with 30 mA residual current protection, 25 A, 2P, 230 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Width":"54 mm","title":"A9TYB4225","Colour":"White (RAL 9003)","Height":"91 mm","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1","description":"Arc fault detection with residual current protection add-on block, Acti9 VigiARC iC60, 2P, 25A, 30mA, type A-SI","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 VigiARC iC60","Mounting mode":"Clip-on","Quality labels":"IMQ","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Range of product":"Acti9","Device short name":"VigiARC iC60","Network frequency":"50 Hz","Poles description":"2P","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"25 A","Electrical durability":"10000 cycles > 25 A 20000 cycles <= 25 A","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals1...10 mm² flexible Tunnel type terminals1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Product or component type":"Arc fault detection with residual current protection add-on block","Threshold tripping voltage":"275 V for +/- 5 V","[Ui] rated insulation voltage":"250 V AC","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$329.99","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/25a1dccddc4084a5a6f4e8b200d671be.pdf","sourceUrl":"https://www.se.com/ae/en/product/A9TYB4225/arc-fault-detection-with-residual-current-protection-addon-block-acti9-vigiarc-ic60-2p-25a-30ma-type-asi/"},"ai":{"faq":[{"question":"What compliance standards does the A9TYB4225 meet?","answer":"The A9TYB4225 complies with EN/IEC 62606 (arc-fault detection), EN/IEC 61009-1, and EN/IEC 61009-2-1 (residual current operated circuit-breakers). It carries IMQ quality label and is tropicalised to severity B per IEC 60068-2-30 for 28 days."},{"question":"Where can I buy the A9TYB4225?","answer":"The A9TYB4225 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the difference between the A9TYB4225 and a standard RCBO?","answer":"The A9TYB4225 adds arc-fault detection (AFDD) per EN/IEC 62606 on top of the residual current protection. A standard RCBO only provides overcurrent and earth-leakage protection; it does not detect series or parallel arcing faults that can cause electrical fires even below the overcurrent trip threshold."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TYB4225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TYB4225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}