{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TYB4625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TYB4625","canonicalUrl":"https://aoctrl.com/schneider/A9TYB4625","factsUrl":"https://aoctrl.com/api/mcp/products/A9TYB4625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 VigiARC iC40, arc fault detection device with residual current protection (AFDD+RCBO), 1P+N, 25 A, 30 mA, Type A-SI, 230 V AC, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9TYB4625 Acti9 VigiARC iC40 is a combined arc fault detection device (AFDD) and residual current circuit breaker with overcurrent protection (RCBO) in a single 36 mm wide, 1P+N module. It is rated at 25 A and 30 mA earth-leakage sensitivity, per the datasheet. The Type A-SI (Super Immunised) residual current protection is voltage-independent, meaning it trips on leakage current alone without needing a separate power supply for the detection circuit. This matters for panel builders: the SI classification handles pulsed DC and high-frequency AC leakage from modern switched-mode loads without nuisance tripping. Clip-on mounting to DIN rail, 2 module pitches (36 mm wide). Neutral on the left. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip length 14 mm, tightening torque 2 N·m. ## Environmental and durability Operating temperature range -25 to 40 °C; storage -40 to 80 °C. Electrical durability: 10,000 cycles above 25 A, 20,000 cycles at or below 25 A. Mechanical durability 20,000 cycles. Local signalling includes ON/OFF/fault trip LED and arc fault diagnostic indicator. Records date and time of fault events with maintenance indicators.","metaTitle":"Schneider Electric A9TYB4625 Acti9 VigiARC iC40, 25 A, 30 mA","metaDescription":"Schneider Electric A9TYB4625 Acti9 VigiARC iC40 arc fault detection device with residual current protection, 25 A, 30 mA, Type A-SI, 1P+N, 230 V AC. Current lifecycle stage. Availa","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 VigiARC iC40","Mounting mode":"Clip-on","Quality labels":"IMQ","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Range of product":"Acti9","Device short name":"VigiARC iC40","Network frequency":"50 Hz","Poles description":"1P + N","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"25 A","Electrical durability":"10000 cycles > 25 A 20000 cycles <= 25 A","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals1...10 mm² flexible Tunnel type terminals1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Product or component type":"Arc fault detection with residual current protection add-on block","Threshold tripping voltage":"275 V for +/- 5 V","[Ui] rated insulation voltage":"250 V AC","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$323.68","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9TYB4625/arc-fault-detection-with-residual-current-protection-addon-block-acti9-vigiarc-ic40-1p+n-25a-30ma-type-asi/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TYB4625/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to A9TYB4625 in the Acti9 family?","answer":"Within the Acti9 VigiARC iC40 range, the primary variant difference is the rated current. The A9TYB4625 is the 25 A version. Other order codes in the same family carry different current ratings (e.g., 16 A, 32 A, 40 A) but share the same 30 mA sensitivity, Type A-SI characteristic, and 1P+N pole configuration. The physical footprint and terminal capacity are identical across the range."},{"question":"Where can I buy A9TYB4625 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for A9TYB4625?","answer":"The part is certified to EN/IEC 62606, EN/IEC 61009-1, and EN/IEC 61009-2-1. It carries the IMQ quality label. Tropicalisation severity B per IEC 60068-2-30 is documented. Standard Schneider declarations of conformity and test reports are available for these standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TYB4625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TYB4625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}