{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9TYBE625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9TYBE625","canonicalUrl":"https://aoctrl.com/schneider/A9TYBE625","factsUrl":"https://aoctrl.com/api/mcp/products/A9TYBE625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Active VigiARC iC40, arc-fault detection + residual current add-on block, 1P+N, 25 A, 30 mA, 230 V AC, clip-on DIN rail.","salesMarkdown":"It's rated 25 A continuous, with a 30 mA earth-leakage sensitivity and a 230 V AC operational voltage, so it catches both series and parallel arc faults plus ground leaks in one unit. The arc-fault detection thresholds trip at 275 V (+/- 5 V), and the earth-leakage protection is Type A-SI (Super Immunised), meaning it resists nuisance tripping from high-frequency inverter noise or transient surges out here in the grease. Mounts via clip-on onto a DIN rail (35 mm per EN 60715). The 1P+N configuration has the neutral on the left. Termination uses tunnel-type terminals: 1 to 16 mm² rigid or 1 to 10 mm² flexible, with a tightening torque of 2 N.m and a 14 mm strip length. Compliance standards include EN/IEC 62606 (arc-fault detection devices), EN/IEC 61009-1, and EN/IEC 61009-2-1 (residual current breakers with overcurrent protection). It carries IMQ quality mark. The unit is tropicalised to Severity B per IEC 60068-2-30 for 28 days, so it holds up in humid environments — a real plus for a lube-tech route where condensation on the panel door is the norm. Electrical durability is rated at 10,000 cycles above 25 A and 20,000 cycles at or below 25 A; mechanical durability is 20,000 cycles. The local signalling includes ON/OFF status, a fault-trip LED, and an arc-fault diagnostic LED, so a field tech can read the fault type without a meter. The device also records date-and-time stamps and maintenance indicators, compatible with EcoStruxure Panel Server concentrators for remote monitoring.","metaTitle":"Schneider Electric A9TYBE625 Acti9 Active VigiARC iC40, 25 A","metaDescription":"Schneider Electric A9TYBE625 Acti9 Active VigiARC iC40 arc-fault detection with residual current protection. Rated 25 A, 30 mA, 230 V AC. Active production. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Width":"36 mm","Colour":"White (RAL 9003)","Height":"91 mm","Accuracy":"Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %","Standards":"EN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 Active VigiARC iC40","Mounting mode":"Clip-on","Quality labels":"IMQ","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Event management":"Overvoltage Earth leakage Overload","Local signalling":"ON, OFF, fault trip LED arc fault diagnostic","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Range of product":"Acti9","Device short name":"VigiARC iC40","Network frequency":"50 Hz","Poles description":"1P + N","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"25 A","Type of measurement":"Voltage Active power Current Power factor","Electrical durability":"10000 cycles > 25 A 20000 cycles <= 25 A","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals1...10 mm² flexible Tunnel type terminals1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Electrical data recording":"Date and time Maintenance indicators","Product or component type":"Active arc fault detection with residual current protection add-on block","Concentrator compatibility":"EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal","Threshold tripping voltage":"275 V for +/- 5 V","[Ui] rated insulation voltage":"250 V AC","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...80 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$359.91","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9TYBE625/active-arc-fault-detection-with-residual-current-protection-addon-block-acti9-active-vigiarc-ic40-1p+n-25a-30ma-type-asi/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9TYBE625/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9TYBE625?","answer":"The A9TYBE625 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer."},{"question":"What compliance documentation does A9TYBE625 carry?","answer":"The A9TYBE625 complies with EN/IEC 62606, EN/IEC 61009-1, and EN/IEC 61009-2-1. It carries the IMQ quality mark and is tropicalised per IEC 60068-2-30 Severity B."},{"question":"What is A9TYBE625's rated current and earth-leakage sensitivity?","answer":"The A9TYBE625 is rated at 25 A continuous with a 30 mA earth-leakage sensitivity, operating at 230 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9TYBE625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9TYBE625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}