{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9V06763","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9V06763","canonicalUrl":"https://aoctrl.com/schneider/A9V06763","factsUrl":"https://aoctrl.com/api/mcp/products/A9V06763","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Acti9 Vigi iC60 add-on RCD, 4P, 63A, 300mA sensitivity, Type A, voltage independent, instantaneous, 73.5mm depth.","salesMarkdown":"The A9V06763: Physical fit: 73.5 mm deep, 108 mm wide, 91 mm high — takes 6 modular pitches (9 mm each) on DIN rail. Clips on, screws directly to the downstream MCB (tunnel terminals, 3.5 N·m torque, wire up to 35 mm² rigid). The 14 mm strip length and left-side neutral position are standard for Acti9, so busbar compatibility is guaranteed when you use the matching comb busbar. Production status is active — no end-of-life notice, no substitution dance. This is a current catalog line. The part is specified for outgoing feeder protection in residential, commercial, and light industrial panels (IP20 enclosure, IP40 in modular cabinet). Standards: EN/IEC 61009-1 and -2-1, pollution degree 3, impulse withstand 6 kV.","metaTitle":"Schneider A9V06763 Acti9 Vigi iC60 63A 300mA RCD 4P, 73.5mm","metaDescription":"Active 4P 63A add-on RCD, Type A, 300mA, voltage independent, instantaneous. Clips to DIN rail, screws onto MCB. 73.5mm deep. Order to spec for BOM fill.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"73.5 mm","Range":"Acti9","Width":"108 mm","Height":"91 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"6","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"3P + N","Tightening torque":"3.5 N.m bottom","[In] rated current":"63 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type A","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"400...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 400...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"Bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$163.59 – $208.28","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/A9V06763/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of A9V06763?","answer":"Depth is 73.5 mm, which is the standard depth for the Acti9 Vigi iC60 range."},{"question":"What range does A9V06763 belong to?","answer":"It's part of the Schneider Acti9 range, specifically the Vigi iC60 series."},{"question":"What compliance standards does A9V06763 meet?","answer":"It complies with EN/IEC 61009-1 and EN/IEC 61009-2-1 for residual current circuit breakers, and IEC 60947-2 for insulation (pollution degree 3) and impulse withstand (6 kV)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9V06763","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9V06763 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}