{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9V11240","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9V11240","canonicalUrl":"https://aoctrl.com/schneider/A9V11240","factsUrl":"https://aoctrl.com/api/mcp/products/A9V11240","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 2P, 40 A, 30 mA, Type AC, clip-on DIN rail.","salesMarkdown":"Rated 40 A with 30 mA sensitivity, Type AC, it provides instantaneous earth-fault protection for 2-pole circuits on 230–240 V AC 50/60 Hz networks. The 30 mA sensitivity is the residual current that triggers the instantaneous trip; this is the standard threshold for personal protection against electric shock in residential and commercial final circuits. ## Panel Integration & Wiring IP20 on the body, IP40 inside a modular enclosure. Rated insulation voltage 500 V AC; rated impulse withstand voltage 6 kV. The 8/20 µs impulse withstand of 250 A per IEC 61009-1 ensures the device does not nuisance-trip on surge currents.","metaTitle":"Schneider Electric A9V11240 Vigi iC60 RCD Add-On Block, 40A","metaDescription":"Schneider Electric A9V11240 Acti9 Vigi iC60 add-on RCD, 2P, 40A, 30mA, Type AC. Obsolete — sourced to order against RFQ. EN/IEC 61009-1. Clip-on DIN rail.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73.5 mm","Range":"Acti9","Width":"72 mm","Height":"91 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"4","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m bottom","[In] rated current":"40 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230...240 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...240 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"Bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/42e5d8ede2453955da0eeb96253159b8.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9V11240/vigi-ic60-earth-leakage-addon-block-2p-40a-30ma-ac-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9V11240/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9V11240 and how do I get a price?","answer":"The A9V11240 is sourced through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is A9V11240's listed depth?","answer":"The depth is 73.5 mm."},{"question":"What is the A9V11240 used for?","answer":"It is an add-on residual current device (RCD) for the Acti9 Vigi iC60 range, providing earth leakage protection (30 mA, Type AC) on 2-pole 40 A circuits in AC distribution boards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9V11240","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9V11240 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}