{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9V11425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9V11425","canonicalUrl":"https://aoctrl.com/schneider/A9V11425","factsUrl":"https://aoctrl.com/api/mcp/products/A9V11425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 4P, 25 A, 30 mA, AC type, clip-on DIN rail, 73.5 mm depth.","salesMarkdown":"Rated 25 A with 30 mA sensitivity, AC type, it provides earth leakage protection for a 4-pole (4P) circuit on a 400 V AC network, 50/60 Hz. The 30 mA sensitivity is the standard threshold for personal protection against direct-contact shock in residential and commercial final circuits, while the instantaneous trip characteristic means it clears a fault within the first half-cycle — no intentional delay for selectivity. The 25 A rated current (In) sets the maximum continuous load the RCD can carry without thermal derating in a 40 °C ambient; the protected circuit's design load must stay below this. The 30 mA sensitivity is the trip threshold for earth leakage current — any imbalance between phase and neutral exceeding 30 mA will cause the device to open within the instantaneous response time. This is the standard for socket-outlet circuits in most IEC-based wiring regulations, providing protection against direct contact with live parts. The voltage-independent tripping technology means the RCD will operate even if the supply voltage is lost — the trip mechanism draws its energy from the fault current itself, a requirement for safety in circuits where the neutral may be interrupted. The A9V11425 clips onto a DIN rail (35 mm) and occupies 6 module pitches (54 mm). It is an add-on block that screws directly to the outgoing side of an iC60 MCB — the electrical connection is made via the screw terminals on the bottom of the RCD, which accept rigid cable up to 25 mm² or flexible cable up to 16 mm² with or without ferrules. The A9V11425 is designed and tested to EN 61009-1 and IEC 61009-1, the standards for residual current operated circuit breakers with integral overcurrent protection (RCBOs) — though this is an add-on block, not a combined unit, the RCD portion follows the same test regime. The device also carries an 8/20 µs impulse withstand rating of 250 A, meaning it can survive a lightning-induced surge current on the residual current path without nuisance tripping or damage.","metaTitle":"Schneider Electric A9V11425 Vigi iC60 RCD Add-on, 4P 25A 30m","metaDescription":"Schneider Electric A9V11425 Acti9 Vigi iC60 add-on residual current device. 4P, 25 A, 30 mA sensitivity, AC type. Obsolete; sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73.5 mm","Range":"Acti9","Width":"54 mm","Height":"91 mm","Standards":"EN 61009-1 IEC 61009-1","9 Mm Pitches":"6","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"2 N.m bottom","[In] rated current":"25 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...25 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz conforming to EN 61009-1 400/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"Bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c54dc1c7c305d04fd662840e38b78d6e.pdf","sourceUrl":"https://www.se.com/uk/en/product/A9V11425/vigi-ic60-earth-leakage-addon-block-4p-25a-30ma-ac-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9V11425/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9V11425?","answer":"The A9V11425 is sourced to order against an RFQ through our network of independent distribution partners. Availability and current pricing are confirmed at quote time. Submit an RFQ for a locate-and-quote response."},{"question":"What is the A9V11425 used for?","answer":"It is an add-on residual current device (RCD) that provides earth leakage protection for a 4-pole, 25 A, 400 V AC circuit. It clips onto a compatible iC60 MCB and trips instantaneously at 30 mA earth leakage, AC type. Typical use is in distribution boards for final sub-circuits requiring personal shock protection."},{"question":"What is the depth of the A9V11425?","answer":"The depth is 73.5 mm. This is the dimension from the front face to the rear of the DIN-rail clip, excluding any protruding terminals or cables."},{"question":"What standards does the A9V11425 comply with?","answer":"It complies with EN 61009-1 and IEC 61009-1 for residual current devices. The rated insulation voltage is 500 V AC per IEC 60947-2, and the impulse withstand voltage is 6 kV. Pollution degree 3 per IEC 60947-2 applies."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9V11425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9V11425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}