{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9V19463","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9V19463","canonicalUrl":"https://aoctrl.com/schneider/A9V19463","factsUrl":"https://aoctrl.com/api/mcp/products/A9V19463","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 4P, 63 A, AC type, selective, 1000 mA, 230...415 V AC, clip-on DIN rail.","salesMarkdown":"The Schneider Electric A9V19463 is an Acti9 Vigi iC60 add-on residual current device — 4P, rated 63 A, AC type, selective time delay, 1000 mA sensitivity. The 1000 mA threshold and selective delay mean it coordinates downstream: it lets transient earth faults ride through and only trips on sustained leakage above that level, keeping nuisance trips off the main incomer. Voltage-independent tripping means it clears a ground fault even if the phase voltage collapses — no auxiliary supply needed. Clip-on mount to standard DIN rail. Width 135 mm (7 x 9 mm pitches), depth 73.5 mm, height 91 mm. Bottom tunnel terminals accept 1...35 mm² rigid or 1...25 mm² flexible; tighten to 3.5 N·m. Strip 14 mm. IP20 on the device body; IP40 inside a modular enclosure. Comb-busbar compatible on the bottom side for daisy-chaining neutrals or phases across a row of Vigi units.","metaTitle":"Schneider Electric A9V19463 Acti9 Vigi iC60, 4P, 63A, AC typ","metaDescription":"Schneider Electric A9V19463 Acti9 Vigi iC60 add-on RCD, 4P, 63A, AC type, selective 1000mA, 230-415VAC. Active lifecycle. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"73.5 mm","Width":"135 mm","Height":"91 mm","Voltage":"230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Product Status":"Active","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Add-on residual current device","Ambient Air Temperature Operation":"-5...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/43b8a1d7e65a28b2beb27b27146cb90d.pdf","sourceUrl":"https://www.se.com/uk/en/product/A9V19463/addon-residual-current-device-acti9-vigi-ic60-4p-63a-ac-type-selective-1000ma-230-415vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9V19463/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9V19463","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9V19463 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}