{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9V25363","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9V25363","canonicalUrl":"https://aoctrl.com/schneider/A9V25363","factsUrl":"https://aoctrl.com/api/mcp/products/A9V25363","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60 add-on residual current device, A9V25363, 3P, 63 A, Type A, selective 300 mA, 230…415 V AC.","salesMarkdown":"The Schneider Electric A9V25363 is an add-on residual current device (RCD) from the Acti9 Vigi iC60 range, designed to clip onto the outgoing side of an iC60 MCB. The selective (time-delayed) characteristic means it holds off for a short period during a fault, allowing downstream RCDs to clear first — essential for discrimination in multi-level distribution boards so a ground fault on a sub-circuit doesn't take out the whole panel. Clip-on mounting onto DIN rail, 7 x 9 mm pitches wide (117 mm). The tunnel-type terminals at the bottom accept 1…35 mm² rigid or 1…25 mm² flexible cable, stripped 14 mm, torqued to 3.5 N·m. Electrical connection to the upstream MCB is by screws — no separate wiring needed for the phase bus. IP20 finger-safe on the front; IP40 inside the modular enclosure once installed. There is no official direct replacement from Schneider — the Acti9 range has evolved, and a parametric substitute would need to be evaluated for fit (same 3P, 63 A, Type A, 300 mA, selective, voltage-independent trip). Rated operational voltage 230…415 V AC, 50/60 Hz — covers single-phase (230 V between phase and neutral) and three-phase (400/415 V between phases) networks common across Europe and much of Asia. Rated insulation voltage 500 V AC, impulse withstand 6 kV per IEC 60947-2. The residual current tripping technology is voltage-independent — it does not need an external power supply to detect a fault and trip. This is a safety advantage: the RCD will still operate even if the neutral is lost or the supply voltage drops. 8/20 µs impulse withstand rated at 3000 A per IEC 61009-1 — the device will not nuisance-trip from lightning-induced surges or switching transients up to that level. Operating temperature range -25…60 °C, storage -40…85 °C — suitable for indoor panel environments in most climates, including unheated enclosures.","metaTitle":"Schneider Electric A9V25363 Acti9 Vigi iC60, 63A, 300mA, Typ","metaDescription":"Schneider Electric A9V25363 Acti9 Vigi iC60 add-on RCD, 3P, 63A, Type A, 300mA selective. Obsolete — sourced to order against RFQ. EN/IEC 61009-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73.5 mm","Range":"Acti9","Width":"117 mm","Height":"91 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"7","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"3.5 N.m bottom","[In] rated current":"63 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type A","Electromagnetic compatibility":"8/20 µs impulse withstand, 3000 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Selective","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"Bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/72f9f8b4f8fa44f46def0e63186973dd.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9V25363/addon-residual-current-device-acti9-vigi-ic60-3p-63a-a-type-selective-300ma-230-415vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9V25363/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9V25363?","answer":"Submit an RFQ. Availability and current pricing are confirmed at quote time through independent distribution channels that carry new-old-stock and qualified surplus inventory."},{"question":"What is the closest alternative to A9V25363 in the Acti9 range?","answer":"Schneider has not published an official direct replacement. A parametric substitute would need to match the 3P, 63 A, Type A, 300 mA selective, voltage-independent trip characteristics. Consult an application engineer for a cross-reference."},{"question":"What compliance documentation does Schneider provide for A9V25363?","answer":"The device is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1 (RCD/MCB combination standards), and IEC 60947-2 for insulation and impulse withstand. Pollution degree 3 per IEC 60947-2. Standard Schneider documentation includes a declaration of conformity covering these standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9V25363","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9V25363 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}