{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9V35263","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9V35263","canonicalUrl":"https://aoctrl.com/schneider/A9V35263","factsUrl":"https://aoctrl.com/api/mcp/products/A9V35263","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 2P, 63 A, 300 mA, Type A-SI (Super Immunised), selective time delay, clip-on DIN rail mount.","salesMarkdown":"It adds earth leakage protection to the circuit, with a rated residual sensitivity of 300 mA and a Type A-SI (Super Immunised) characteristic — meaning it handles pulsed DC earth faults and is immune to nuisance tripping from high-frequency harmonics or transient surges common on modern electronic loads. Rated at 63 A (In) and 230…415 V AC (Ue), this 2-pole block is sized for the outgoing feeder of a single-phase or three-phase sub-distribution board. The selective (time-delayed) earth-leakage protection means it coordinates with downstream RCDs — it will hold during a momentary fault on a branch circuit, letting the downstream device clear first, then trip if the fault persists. This avoids a full-board blackout for a single branch fault. The voltage-independent residual current tripping technology means the RCD operates without needing a separate power supply; it uses the fault current itself to trigger the mechanism. This is a reliability advantage in installations where the neutral could be lost upstream. The bottom tunnel terminals accept 1…35 mm² rigid or 1…25 mm² flexible cable, with a tightening torque of 3.5 N·m. The 14 mm strip length is standard for this terminal class. A comb busbar can feed the bottom terminals, simplifying multi-pole distribution. Designed and certified to EN/IEC 61009-1 and EN/IEC 61009-2-1 (the RCD/MCB combination standards). Rated insulation voltage (Ui) 500 V AC, impulse withstand (Uimp) 6 kV. The 8/20 µs impulse withstand of 3000 A confirms it survives lightning-induced surge currents without damage.","metaTitle":"A9V35263 Vigi iC60 RCD Add-On Block, 2P 63A 300mA SI Type","metaDescription":"Schneider Electric Acti9 Vigi iC60 add-on RCD block. 2P, 63A, 300mA, Type A-SI, selective. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"73.5 mm","Width":"72 mm","Height":"91 mm","Voltage":"230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Product Status":"Active","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Add-on residual current device","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/41a7d59f3000478051116a43764b394d.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9V35263/vigi-ic60-earth-leakage-addon-block-2p-63a-300ma-si-type-selective/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9V35263/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9V35263","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9V35263 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}