{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9W12263","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9W12263","canonicalUrl":"https://aoctrl.com/schneider/A9W12263","factsUrl":"https://aoctrl.com/api/mcp/products/A9W12263","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 2P, 63 A, 100 mA, Type AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9W12263 is an Acti9 Vigi iC60 add-on residual current device (RCD) — a voltage-independent earth leakage block that clips onto the outgoing side of an iC60 MCB to provide ground-fault protection in a 2-pole (2P) configuration. Rated at 63 A with 100 mA sensitivity, Type AC (sinusoidal AC residual currents only), it operates on 230/400 V AC 50/60 Hz networks and meets EN 61009-1 and IEC 61009-1. Mounts via clip-on to DIN rail (4 x 9 mm pitches), with tunnel-type terminals accepting up to 35 mm² rigid or 25 mm² flexible cable, tightened to 3.5 N·m. The A9W12263 is marked Obsolete by Schneider Electric. 63 A rated current and 100 mA earth leakage sensitivity: this block pairs with a 63 A iC60 MCB to protect a final subcircuit (outgoer) where the required fault protection threshold is 100 mA — typical for socket-outlet circuits or general-purpose loads where 30 mA is not mandated. It is not suitable for pulsating DC or smooth DC fault currents — those require Type A or Type B devices respectively. Voltage-independent tripping technology means the RCD operates without needing a separate power supply; it uses the fault current itself to trigger the mechanism, which improves reliability if the supply voltage is lost. Clip-on mounting to DIN rail and screw connection to the adjacent iC60 MCB — the block is designed as a side-by-side add-on, not a standalone device. It occupies 4 module pitches (72 mm width) on the rail. Local signalling via a trip indicator provides visual confirmation of a residual current trip event, aiding fault isolation during commissioning or troubleshooting. Rated impulse withstand voltage of 6 kV (IEC 60947-2) and insulation voltage of 500 V AC — coordinates with standard distribution board surge ratings.","metaTitle":"A9W12263 Acti9 Vigi iC60 RCD Add-on Block, 2P 63A 100mA AC T","metaDescription":"Schneider Electric A9W12263 Acti9 Vigi iC60 add-on residual current device. 2P, 63A, 100mA, Type AC. Obsolete — sourced to order against RFQ. EN/IEC 61009-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"72 mm","Height":"91 mm","Standards":"EN 61009-1 IEC 61009-1","9 Mm Pitches":"4","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m","[In] rated current":"63 A","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals downside 1...35 mm² rigid Tunnel type terminals downside 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230/400 V AC 50/60 Hz conforming to EN 61009-1 230/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1a1f47dc0aeef868c2f7c210fb37a029.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9W12263/vigi-ic60-earth-leakage-addon-block-2p-63a-100ma-ac-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9W12263/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9W12263?","answer":"Submit an RFQ through this listing. The part is sourced to order via independent distribution channels; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to A9W12263 in the Acti9 family?","answer":"No official successor order code is listed. A functionally similar replacement would be a current-production Acti9 Vigi iC60 add-on block with matching pole count (2P), current rating (63 A), sensitivity (100 mA), and Type AC characteristic — verify physical fit and terminal compatibility before substituting."},{"question":"What compliance documentation does this brand provide for A9W12263?","answer":"The part is certified to EN 61009-1 and IEC 61009-1. Pollution degree 3 per IEC 60947-2. IP20/IP40 per IEC 60529. No RoHS or REACH statements are in the available records."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9W12263","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9W12263 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}