{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9W14325","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9W14325","canonicalUrl":"https://aoctrl.com/schneider/A9W14325","factsUrl":"https://aoctrl.com/api/mcp/products/A9W14325","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60 add-on residual current device, 3P, 25 A, 300 mA, Type AC, clip-on DIN rail mount, 74 mm depth.","salesMarkdown":"It is a 3-pole unit rated 25 A with 300 mA sensitivity, Type AC (sinusoidal AC fault currents only). The 25 A rated current (In) and 300 mA earth-leakage sensitivity define the protection envelope: the block sits downstream of a 25 A iC60 MCB and trips on residual currents above 300 mA. Type AC detection covers sinusoidal AC faults only — not pulsed DC or smooth DC, which is the limitation to watch if your load includes VFDs, UPS systems, or LED drivers that can generate non-sinusoidal leakage. Rated operational voltage is 400 V AC (400/415 V AC per IEC 61009-1), insulation voltage 500 V AC, and impulse withstand 6 kV — all consistent with standard 3-phase distribution in a 400 V TN or IT system. The voltage-independent tripping technology means the RCD operates without needing a separate power supply; it draws its trip energy from the fault current itself. IP20 on the body (finger-safe), IP40 inside a modular enclosure. Clip-on mounting to DIN rail, with screw connection to the upstream MCB. Tightening torque 2 N·m, strip length 14 mm. The 74 mm depth keeps the assembly within standard distribution board clearances. Instantaneous trip (no time delay) and 8/20 µs impulse withstand of 250 A per IEC 61009-1. The trip indicator gives local visual confirmation of which device has operated — useful during fault-finding on a multi-circuit panel.","metaTitle":"A9W14325 Vigi iC60 Earth Leakage Add-on Block, 3P 25A 300mA","metaDescription":"A9W14325 Acti9 Vigi iC60 add-on RCD block, 3P, 25A, 300mA, Type AC. Obsolete — sourced to order against RFQ. IEC 61009-1, EN 61009-1. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"108 mm","Height":"91 mm","Standards":"IEC 61009-1 EN 61009-1","9 Mm Pitches":"6","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"2 N.m","[In] rated current":"25 A","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals downside 1...25 mm² rigid Tunnel type terminals downside 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz conforming to EN 61009-1 400/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6e7efaeafa852bfc39562660d5d6eb5a.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9W14325/vigi-ic60-earth-leakage-addon-block-3p-25a-300ma-ac-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9W14325/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9W14325 and get a price?","answer":"A9W14325 is sourced through independent distribution channels. Submit an RFQ — availability and current pricing are confirmed at quote time. No stock or price figures are published for this obsolete line."},{"question":"What are the key ratings of A9W14325?","answer":"3-pole, 25 A rated current, 300 mA earth-leakage sensitivity, Type AC, rated operational voltage 400 V AC, instantaneous trip, voltage-independent tripping technology. Mounts on DIN rail, 74 mm depth."},{"question":"What standards does A9W14325 comply with?","answer":"IEC 61009-1 and EN 61009-1 for residual current operated circuit-breakers. Pollution degree 3 per IEC 60947-2. IP20 (body), IP40 (in modular enclosure)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9W14325","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9W14325 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}