{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9W14363","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9W14363","canonicalUrl":"https://aoctrl.com/schneider/A9W14363","factsUrl":"https://aoctrl.com/api/mcp/products/A9W14363","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, earth leakage add-on block, 3P, 63 A, 300 mA, AC type, clip-on DIN rail mount, IP20.","salesMarkdown":"It adds 300 mA AC-type earth leakage protection to a 3-pole 63 A circuit, tripping instantaneously when residual current exceeds that threshold. Rated at 63 A (In) and 300 mA sensitivity, this block is sized for a subfeed or outgoing circuit where the upstream MCB is already 63 A — the add-on does not increase the interrupting rating, it adds leakage detection. Voltage-independent trip technology means the block operates without needing a separate power supply — it uses the line energy to trip. Designed to IEC 61009-1 and EN 61009-1 (RCCB/MCB combination standards), with a rated insulation voltage of 500 V AC and rated operational voltage of 230/415 V AC at 50/60 Hz. Impulse withstand voltage is 6 kV per IEC 60947-2, and pollution degree 3 per the same standard. IP20 rated for the block body; IP40 in a modular enclosure. Clip-on mount to DIN rail, 7 x 9 mm pitch modules wide (117 mm). The block connects to the iC60 MCB via screws — no busbar required, but the mechanical interlock is specific to the Vigi iC60 range. The A9W14363 is marked obsolete by Schneider Electric. Any requalification for a substitute should account for the mechanical fit to the iC60 MCB and the AC-type trip characteristic.","metaTitle":"A9W14363 Vigi iC60 Earth Leakage Add-on Block, 63A 300mA AC","metaDescription":"Schneider Electric A9W14363 Acti9 Vigi iC60 earth leakage add-on block, 3P, 63 A, 300 mA, AC type. Obsolete — sourced to order. IEC 61009-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"117 mm","Height":"91 mm","Standards":"IEC 61009-1 EN 61009-1","9 Mm Pitches":"7","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"3.5 N.m","[In] rated current":"63 A","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals downside 1...35 mm² rigid Tunnel type terminals downside 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6f11cf3af341d7db0d125a67a3f93127.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9W14363/vigi-ic60-earth-leakage-addon-block-3p-63a-300ma-ac-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9W14363/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9W14363?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of A9W14363?","answer":"63 A rated current, 300 mA earth leakage sensitivity, AC type, voltage-independent trip, instantaneous time delay, 230/415 V AC operational voltage, 6 kV impulse withstand."},{"question":"What compliance standards does A9W14363 meet?","answer":"IEC 61009-1, EN 61009-1, and IEC 60947-2 (pollution degree 3)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9W14363","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9W14363 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}