{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9W24425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9W24425","canonicalUrl":"https://aoctrl.com/schneider/A9W24425","factsUrl":"https://aoctrl.com/api/mcp/products/A9W24425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 4P, 25 A, 300 mA, Type A, clip-on DIN rail, obsolete.","salesMarkdown":"The Schneider Electric A9W24425 is an Acti9 Vigi iC60 add-on residual current device — 4 poles, rated 25 A, with 300 mA Type A earth-leakage sensitivity. Voltage-independent tripping means the RCD detects leakage even if the phase voltage collapses, which matters on circuits where a lost neutral could otherwise blind the protection. Rated 25 A at 230/415 V AC, 50/60 Hz, 4-pole outgoing feeder. 300 mA sensitivity is instantaneous, suitable for fire or equipment protection. Type A detects pulsating DC residual currents. Rated insulation voltage 500 V AC and impulse withstand 6 kV per IEC 60947-2, with an 8/20 µs surge capacity of 250 A per IEC 61009-1. That means it holds up through standard distribution-level transients without nuisance tripping or internal flashover. Clip-on mounting to DIN rail, 6 module pitches wide (126 mm). IP20 on the device body, IP40 inside a modular enclosure — fine for dry indoor panels, not for washdown areas. Designed and tested to IEC 61009-1 and EN 61009-1 — the harmonized standard for residual-current-operated circuit-breakers with integral overcurrent protection (though this is the add-on RCD module, not the combined breaker). The 8/20 µs impulse-withstand rating and the voltage-independent trip technology are both part of that standard's requirements.","metaTitle":"A9W24425 Acti9 Vigi iC60 4P 25A 300mA RCD, Obsolete","metaDescription":"Schneider Electric A9W24425 Acti9 Vigi iC60 add-on RCD, 4P, 25A, 300mA, Type A. Obsolete — sourced to order against RFQ. IEC 61009-1, clip-on DIN rail.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"126 mm","Height":"91 mm","Standards":"IEC 61009-1 EN 61009-1","9 Mm Pitches":"6","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"2 N.m","[In] rated current":"25 A","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals downside 1...25 mm² rigid Tunnel type terminals downside 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type A","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1e7d0e1c032aea7623daf3ed646abe1.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9W24425/addon-residual-current-device-acti9-vigi-ic60-4p-25a-300ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9W24425/alternatives.json"},"ai":{"faq":[{"question":"What is A9W24425 used for?","answer":"It is an add-on residual current device (RCD) for the Acti9 iC60 MCB, providing 300 mA Type A earth-leakage protection on a 4-pole, 25 A outgoing circuit. Typical use: fire protection or equipment protection on three-phase submain feeders, or large single-phase loads where neutral protection is needed."},{"question":"What compliance documentation does Schneider provide for A9W24425?","answer":"The device is designed to IEC 61009-1 and EN 61009-1. The evidence does not list RoHS, REACH, or UL documentation specifically for this order code. Standard Schneider Acti9 series compliance documentation would apply; confirm with the supplier at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9W24425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9W24425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}