{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9W24463","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9W24463","canonicalUrl":"https://aoctrl.com/schneider/A9W24463","factsUrl":"https://aoctrl.com/api/mcp/products/A9W24463","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60 add-on residual current device, 4P, 63A, Type A, 300 mA, instantaneous, 230/415 V AC, for iC60 double terminal.","salesMarkdown":"It provides earth-leakage protection for a 4P circuit rated at 63 A continuous current, with a 300 mA sensitivity and Type A waveform recognition — meaning it trips on sinusoidal AC residual currents and pulsating DC residual currents, which covers most modern electronic loads like variable-speed drives, switched-mode power supplies, and rectifiers. The instantaneous trip characteristic (no intentional time delay) ensures fast disconnection on fault, making it suitable for final subcircuits where selectivity with upstream delayed RCDs is managed by grading, not by this device itself. The voltage-independent trip technology means the RCD does not rely on the supply voltage or an external power source to operate — the fault current itself provides the energy to trip, which is a safety advantage if the neutral is lost or the voltage collapses during a fault. This is a key distinction from electronic RCDs that require a power supply to function. The unit occupies 7 modules of 9 mm pitch, so 63 mm of DIN rail width. Dimensions are 135 mm wide × 91 mm high × 74 mm deep. The electrical connection to the MCB is made by screws, so verify the iC60 double-terminal accessory is present on the breaker before assembly. IP20 per IEC 60529 for the device body; IP40 when enclosed in a modular enclosure. Storage temperature range -40…85 °C, operating -25…60 °C. Designed and certified to IEC 61009-1 and EN 61009-1, the harmonized standard for residual current operated circuit breakers with integral overcurrent protection (RCBOs) — though this unit is an add-on RCD, not a combined RCBO. The impulse withstand rating is 250 A at 8/20 µs waveform per IEC 61009-1. Rated insulation voltage 500 V AC; rated impulse withstand voltage 6 kV per IEC 60947-2. These standards ensure the device meets European and international installation codes for residual current protection.","metaTitle":"Schneider Electric A9W24463 Vigi iC60 RCD, 63A 300mA Type A","metaDescription":"Add-on residual current device, Acti9 Vigi iC60, 4P, 63A, Type A, 300mA, 230/415VAC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"135 mm","Height":"91 mm","Standards":"IEC 61009-1 EN 61009-1","9 Mm Pitches":"7","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"3.5 N.m","[In] rated current":"63 A","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals downside 1...35 mm² rigid Tunnel type terminals downside 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type A","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d51197f23089783f470a40e07a4d01f6.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9W24463/addon-residual-current-device-acti9-vigi-ic60-4p-63a-a-type-instantaneous-300ma-230-415vac-for-ic60-double-terminal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9W24463/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9W24463 and get a price?","answer":"The A9W24463 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response."},{"question":"What does Type A earth leakage protection mean on this RCD?","answer":"Type A means the device trips on sinusoidal AC residual currents and on pulsating DC residual currents up to 6 mA of smooth DC superimposed. This covers most modern non-linear loads such as single-phase rectifiers, switched-mode power supplies, and variable-speed drives — the dominant fault signature in contemporary industrial and commercial installations."},{"question":"What is the depth of the A9W24463?","answer":"The depth is 74 mm. Combined with the 135 mm width and 91 mm height, it occupies 7 DIN-rail modules (63 mm) of panel space."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9W24463","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9W24463 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}