{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9W26225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9W26225","canonicalUrl":"https://aoctrl.com/schneider/A9W26225","factsUrl":"https://aoctrl.com/api/mcp/products/A9W26225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 2P, 25 A, 500 mA, Type A, voltage-independent, instantaneous, DIN-rail clip-on.","salesMarkdown":"The A9W26225 is a Vigi iC60 add-on residual current device (RCD) from the Acti9 range. It clips onto the downstream side of an iC60 MCB to add earth-leakage protection to the outgoing circuit. The kit is complete — the block ships with its own tunnel-type terminals and screws for the mechanical and electrical link to the MCB; no separate accessory pack needed. Rated for 25 A continuous on a 230/415 V AC network at 50/60 Hz, it provides 500 mA earth-leakage sensitivity with Type A protection — meaning it detects sinusoidal AC residual currents plus pulsating DC residual currents, which covers most modern electronic loads. The trip is instantaneous (no intentional delay), so it clears ground faults immediately. The residual current tripping is voltage-independent — the block does not need an external power supply to operate; it draws its trip energy from the fault current itself. This makes it inherently reliable even if the supply voltage drops during a fault. ## Integration and fit It occupies 3 x 9 mm pitches (27 mm) of DIN-rail width. The tunnel-type terminals on the downside accept 1…25 mm² rigid or 1…16 mm² flexible cable; wire stripping length is 14 mm; tightening torque is 2 N·m. IP20 rated (finger-safe) on the front face; IP40 inside a modular enclosure. Operating temperature range is -25…60 °C; storage range -40…85 °C. Designed and tested to IEC 61009-1 and EN 61009-1 (RCBO standard for household and similar installations). Rated insulation voltage 500 V AC; rated impulse withstand voltage 6 kV per IEC 60947-2. The block withstands 8/20 µs impulse currents up to 250 A per IEC 61009-1.","metaTitle":"A9W26225 Acti9 Vigi iC60 Earth Leakage Add-on Block, 2P 25A","metaDescription":"A9W26225 Acti9 Vigi iC60 add-on residual current device. 2P, 25A, 500mA sensitivity, Type A. Obsolete — sourced to order against RFQ. IEC 61009-1. DIN rail clip-on.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"63 mm","Height":"91 mm","Standards":"IEC 61009-1 EN 61009-1","9 Mm Pitches":"3","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"2 N.m","[In] rated current":"25 A","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals downside 1...25 mm² rigid Tunnel type terminals downside 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"500 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type A","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"230/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8940f200dff842255dc5032492178e6e.pdf","sourceUrl":"https://www.se.com/uk/en/product/A9W26225/vigi-ic60-earth-leakage-addon-block-2p-25a-500ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9W26225/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9W26225 and how is it quoted?","answer":"We source A9W26225 through our multi-supplier network and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock or lead-time figures on this page. Submit an RFQ for a firm commercial posture."},{"question":"What is the closest alternative to A9W26225 in the Acti9 range?","answer":"No official successor is listed in the lifecycle record. The Acti9 range continues with current Vigi iC60 variants, but pin-compatibility and mechanical fit should be verified against the specific iC60 MCB frame and the panel wiring. Submit an RFQ with your application details for cross-reference support."},{"question":"What compliance documentation is available for A9W26225?","answer":"The product is designed to IEC 61009-1 and EN 61009-1. The evidence does not list RoHS, REACH, UL, or CSA certifications for this specific order code. Compliance documentation is confirmed at quote time against your jurisdiction."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9W26225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9W26225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}