{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9W26325","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9W26325","canonicalUrl":"https://aoctrl.com/schneider/A9W26325","factsUrl":"https://aoctrl.com/api/mcp/products/A9W26325","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC60, add-on residual current device, 3P, 25 A, 500 mA, Type A, instantaneous, voltage independent, clip-on DIN rail, IP20/IP40, 74 mm depth.","salesMarkdown":"The Schneider Electric A9W26325 is an Acti9 Vigi iC60 add-on residual current device (RCD) — a 3-pole, 25 A, 500 mA, Type A earth-leakage block designed to clip onto the downstream side of an iC60 MCB. It is voltage independent, meaning it trips on residual current even if the line voltage is lost, and it provides instantaneous protection (no intentional time delay). The unit occupies 6 x 9 mm pitches on a DIN rail, with a depth of 74 mm, width 108 mm, and height 91 mm. The A9W26325 is listed as Obsolete by the manufacturer. If your project is still in design, a qualified alternative from the same Acti9 family should be evaluated to avoid future requalification churn. The 25 A rated current (In) and 500 mA earth-leakage sensitivity define the load and protection profile: this block protects a 25 A outgoing circuit against ground faults above half an amp. Type A detection covers sinusoidal AC and pulsating DC residual currents — the standard for most single-phase electronics and motor drives. The instantaneous trip (no delay) means it will clear a fault in under a cycle, but it also means nuisance tripping on circuits with high inrush or capacitive leakage; that is a design constraint to check before specifying. The voltage-independent trip mechanism is an advantage on circuits where the supply may be interrupted before the fault clears. ## Panel Integration & Wiring The unit is rated IP20 (finger-safe) and IP40 inside a modular enclosure. The trip indicator gives local visual confirmation of a residual-current trip, which aids fault isolation on a multi-circuit panel. ## Standards & Electrical Ratings Designed and tested to IEC 61009-1 and EN 61009-1 (RCBO standard). Rated operational voltage (Ue) is 400 V AC 50/60 Hz per EN 61009-1, or 230/415 V AC per IEC 61009-1. Rated insulation voltage (Ui) is 500 V AC. Impulse withstand voltage (Uimp) is 6 kV. The unit also withstands 8/20 µs impulse currents up to 250 A per IEC 61009-1. Storage temperature range -40…85 °C; operating -25…60 °C.","metaTitle":"A9W26325 Acti9 Vigi iC60 3P 25A 500mA Type A RCD, Obsolete","metaDescription":"A9W26325 Acti9 Vigi iC60 add-on RCD, 3P, 25 A, 500 mA, Type A. Obsolete per manufacturer. Sourced to order against RFQ. IEC 61009-1, EN 61009-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"108 mm","Height":"91 mm","Standards":"IEC 61009-1 EN 61009-1","9 Mm Pitches":"6","Network type":"AC","Product name":"Acti9 Vigi iC60","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi iC60","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"2 N.m","[In] rated current":"25 A","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals downside 1...25 mm² rigid Tunnel type terminals downside 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"500 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type A","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to IEC 61009-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz conforming to EN 61009-1 230/415 V AC 50/60 Hz conforming to IEC 61009-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2706e28951a8afa5a6ad4fb937cc9823.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9W26325/vigi-ic60-earth-leakage-addon-block-3p-25a-500ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9W26325/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9W26325?","answer":"The A9W26325 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of A9W26325?","answer":"3-pole, 25 A rated current, 500 mA earth-leakage sensitivity, Type A, instantaneous, voltage independent, rated operational voltage 400 V AC, insulation voltage 500 V AC, impulse withstand 6 kV."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9W26325","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9W26325 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}