{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Y85625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Y85625","canonicalUrl":"https://aoctrl.com/schneider/A9Y85625","factsUrl":"https://aoctrl.com/api/mcp/products/A9Y85625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC40 add-on residual current device, A9Y85625, 1P+N, 25 A rated, 300 mA sensitivity, Type A-SI super immunised, voltage independent, clip-on DIN rail.","salesMarkdown":"Rated at 25 A (In) and 300 mA sensitivity, this 1P+N unit is voltage-independent — it trips on residual current regardless of the mains voltage, making it suitable for circuits where voltage may be unstable or where the RCD must operate even with a lost neutral. The Type A-SI (Super Immunised) classification means it handles pulsed DC fault currents (from electronics like VFDs, LED drivers, or UPS) and is immune to nuisance tripping from high-frequency leakage typical of modern switched-mode loads. Instantaneous trip, no intentional delay. Two 9 mm pitches wide (18 mm total) — the 36 mm width fits two standard modular slots. Clip-on mounting onto a DIN rail, neutral on the left. Tunnel-type terminals accept 1…16 mm² rigid or 1…10 mm² flexible at the bottom; tighten to 2 N·m. Ambient operating range -25…60 °C, storage -40…85 °C, altitude up to 2000 m.","metaTitle":"Schneider Electric A9Y85625 Acti9 Vigi iC40 RCD, 25 A, 300 m","metaDescription":"Schneider Electric A9Y85625 Acti9 Vigi iC40 add-on RCD. 25 A rated, 300 mA sensitivity, Type A-SI super immunised. Voltage independent, clip-on DIN rail. Current production. Source","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"95 mm","Standards":"EN/IEC 61009-2-1","9 Mm Pitches":"2","Network type":"AC","Product name":"Acti9 Vigi iC40","Mounting mode":"Clip-on","Quality labels":"OVE","lifecycle_stage":"current","Local signalling":"Fault indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 61009-2-1","Device short name":"Vigi iC40","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m bottom","Operating altitude":"2000 m","[In] rated current":"25 A","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal bottom 1...16 mm² rigid Tunnel type terminal bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","[Ui] rated insulation voltage":"400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 61009-2-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9Y85625/addon-residual-current-device-acti9-vigi-ic40-1p+n-25a-asi-type-instantaneous-300ma-230vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Y85625/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9Y85625?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the residual current sensitivity of A9Y85625?","answer":"300 mA, Type A-SI (Super Immunised), voltage independent, instantaneous trip."},{"question":"What standards does A9Y85625 comply with?","answer":"EN/IEC 61009-2-1 for RCDs, with a rated impulse withstand voltage of 4 kV and pollution degree 3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Y85625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Y85625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}