{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Y87625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Y87625","canonicalUrl":"https://aoctrl.com/schneider/A9Y87625","factsUrl":"https://aoctrl.com/api/mcp/products/A9Y87625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi iC40 A9Y87625, add-on residual current device, 1P+N, 25 A, 30 mA, Type A-G, 230 V AC, clip-on DIN rail.","salesMarkdown":"It protects a single outgoing 1P+N circuit at 230 V AC, 50/60 Hz, with a rated current of 25 A and an earth-leakage sensitivity of 30 mA. The voltage-independent tripping mechanism means the RCD operates without needing a separate power supply or electronic circuit — the fault current itself energizes the trip solenoid, which improves reliability in degraded voltage conditions. ## Integration into a panel The add-on design occupies one modular space to the right of its paired MCB; the two units are linked by screws through the side terminals. Bottom tunnel terminals accept 1…16 mm² rigid or 1…10 mm² flexible cable, stripped 14 mm, tightened to 2 N·m. The white housing carries a local fault-indication flag that shows after a trip, aiding troubleshooting without a meter. Rated insulation voltage 400 V AC, impulse withstand 4 kV — both conforming to EN/IEC 61009-2-1, which governs the safety and performance of residual current operated circuit-breakers with integral overcurrent protection (RCBOs). Ambient operating range -25…60 °C, storage -40…85 °C, with 95 % relative humidity at 55 °C. Maximum operating altitude 2000 m. The electrical endurance is rated at 10,000 cycles, mechanical at 20,000 cycles — figures that reflect the device's intended use as a protective device with infrequent manual operation.","metaTitle":"A9Y87625 Acti9 Vigi iC40 25A 30mA RCBO, 1P+N","metaDescription":"Schneider Electric A9Y87625 Acti9 Vigi iC40 add-on RCBO. 25 A rated, 30 mA Type A-G earth leakage, 230 V AC, voltage-independent tripping. Current production. Sourced to order agai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"95 mm","Standards":"EN/IEC 61009-2-1","9 Mm Pitches":"4","Network type":"AC","Product name":"Acti9 Vigi iC40","Mounting mode":"Clip-on","Quality labels":"OVE","lifecycle_stage":"current","Local signalling":"Fault indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 61009-2-1","Device short name":"Vigi iC40","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m bottom","Operating altitude":"2000 m","[In] rated current":"25 A","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal bottom 1...16 mm² rigid Tunnel type terminal bottom 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","[Ui] rated insulation voltage":"400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Earth-leakage protection class":"Type A-G","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 61009-2-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9Y87625/addon-residual-current-device-acti9-vigi-ic40-1p+n-25a-ag-type-instantaneous-30ma-230vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Y87625/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9Y87625?","answer":"Submit an RFQ against the A9Y87625; our sourcing desk confirms current pricing and availability at quote time through independent distribution channels."},{"question":"What is the closest alternative to A9Y87625 in the Acti9 range?","answer":"The A9Y87625 is the add-on residual current device variant in the Acti9 Vigi iC40 range. The closest alternative would be a different sensitivity (e.g., 300 mA for fire protection) or a different pole configuration (e.g., 2P, 3P, 4P) within the same Vigi iC40 family, but no single pin-compatible drop-in exists — the paired MCB must also match the Vigi iC40 mechanical interface."},{"question":"What is the A9Y87625's depth?","answer":"The A9Y87625 has a depth of 74 mm, with a width of 36 mm (4 x 9 mm pitches) and a height of 95 mm."},{"question":"What compliance documentation does the A9Y87625 carry?","answer":"The A9Y87625 is designed and tested to EN/IEC 61009-2-1, carries OVE quality label, and is rated for pollution degree 3 per that standard. The manufacturer provides a Declaration of Performance (DoP) and CE marking documentation on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Y87625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Y87625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}