{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Z21480","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Z21480","canonicalUrl":"https://aoctrl.com/schneider/A9Z21480","factsUrl":"https://aoctrl.com/api/mcp/products/A9Z21480","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iID, Residual current circuit breaker (RCCB), 4P, 80 A, 30 mA, Type A, 380...415 V AC, clip-on DIN rail.","salesMarkdown":"## What it is and what it does The Schneider Electric A9Z21480 is an Acti9 iID residual current circuit breaker (RCCB) — a 4-pole unit rated 80 A with 30 mA earth-leakage sensitivity, Type A protection, for 380...415 V AC networks at 50/60 Hz. It clips onto a DIN rail, neutral on the left, and uses a voltage-independent trip mechanism so it clears a ground fault even if the phase voltage collapses. ## What the ratings mean for fit 80 A rated current (In) and 30 mA sensitivity is the standard residential/commercial main-switch RCCB spec — it protects the whole downstream board against earth faults while carrying the full load. Type A means it detects pulsating DC residual currents from rectified loads (switched-mode supplies, variable-speed drives, LED drivers) that a plain AC type would miss. Rated conditional short-circuit current is 10 kA (IEC 61008-1), so it withstands a bolted fault up to that level without rupturing, provided the upstream MCB or fuse limits let-through energy. Breaking capacity Idm/Im is 1500 A — that is the RCCB's own ability to interrupt a fault, not the full SCCR; the 10 kA figure governs the installation's fault-withstand rating. Pollution degree 3 means it is rated for conductive pollution or dry non-conductive pollution that becomes conductive due to condensation — typical for industrial control panels and distribution boards not in a sealed clean environment. IP20 body, IP40 in a modular enclosure: no washdown rating, so keep it inside a cabinet.","metaTitle":"Schneider Electric A9Z21480 Acti9 iID RCCB, 80A 30mA 4P","metaDescription":"Schneider Electric A9Z21480 Acti9 iID RCCB, 80A rated current, 30mA earth-leakage sensitivity, 4P, Type A, 380-415V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 61008-1 EN/IEC 61008-2-1","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iID","Mounting mode":"Clip-on","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Device short name":"iID","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"80 A","Electrical durability":"AC-1: 10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"380...415 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 1500 A Im 1500 A","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV","Rated conditional short-circuit current":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/A9Z21480/residual-current-circuit-breaker-rccb-acti9-iid-4p-80a-a-type-30ma-double-terminal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Z21480/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for A9Z21480?","answer":"Submit an RFQ. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What standards does A9Z21480 comply with?","answer":"It complies with EN/IEC 61008-1 and EN/IEC 61008-2-1, the governing standards for residual current operated circuit-breakers without integral overcurrent protection."},{"question":"What is the ambient temperature range for operation?","answer":"Operating ambient air temperature is -25 to 60 °C; storage range is -40 to 85 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Z21480","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Z21480 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}