{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Z22463","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Z22463","canonicalUrl":"https://aoctrl.com/schneider/A9Z22463","factsUrl":"https://aoctrl.com/api/mcp/products/A9Z22463","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iID, Residual current circuit breaker (RCCB), 4P, 63 A, 100 mA, Type A, 380-415 V AC, clip-on DIN rail, IP20/IP40.","salesMarkdown":"The 63 A rated current and 100 mA sensitivity make it suitable for general-purpose branch-circuit protection in commercial and industrial AC networks at 380-415 V, 50/60 Hz. The 63 A rated current (In) is the continuous load the RCCB can carry without tripping under healthy conditions — sized for a feeder or submain, not for final subcircuits below 20 A. The 100 mA earth-leakage sensitivity is a protection threshold for equipment or circuits where a 30 mA device would nuisance-trip due to natural leakage (e.g., long cable runs, heaters, or multiple loads). Type A detection covers sinusoidal AC residual currents and pulsating DC residual currents up to 6 mA smooth DC — the minimum for circuits with single-phase rectifiers, switching power supplies, or variable-speed drives. The instantaneous trip (no intentional delay) means it clears earth faults within tens of milliseconds; this is standard for personnel protection but must be coordinated with upstream time-delayed RCCBs or RCBOs to avoid cascade tripping. Breaking capacity Idm is 1500 A (Im also 1500 A), and the rated conditional short-circuit current (Icn) is 10 kA — meaning the RCCB can withstand a 10 kA fault without damage when protected by an upstream fuse or MCB of appropriate rating. Neutral is on the left (fixed position). Wire stripping length is 14 mm for both top and bottom connections. The toggle control has a contact-position indicator and accepts a padlocking device for lockout/tagout.","metaTitle":"Schneider Electric A9Z22463 Acti9 iID RCCB, 63A, 100mA, Type","metaDescription":"Schneider Electric A9Z22463 Acti9 iID 4P RCCB, 63 A rated current, 100 mA sensitivity, Type A, 380-415 V AC, 10 kA SCCR, instantaneous trip. Active production, sourced to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 61008-1 EN/IEC 61008-2-1","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iID","Mounting mode":"Clip-on","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Device short name":"iID","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"63 A","Electrical durability":"AC-1: 15000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Earth-leakage sensitivity":"100 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"380...415 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 1500 A Im 1500 A","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV","Rated conditional short-circuit current":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/A9Z22463/residual-current-circuit-breaker-rccb-acti9-iid-4p-63a-a-type-100ma-double-terminal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Z22463/alternatives.json"},"ai":{"faq":[{"question":"What is the A9Z22463 used for?","answer":"It is a four-pole residual current circuit breaker (RCCB) rated 63 A, 100 mA sensitivity, Type A, for earth-leakage protection on 380-415 V AC three-phase networks in commercial and industrial distribution boards."},{"question":"Where can I buy the A9Z22463?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for the A9Z22463?","answer":"The part is designed to EN/IEC 61008-1 and EN/IEC 61008-2-1 standards. It carries IP20 and IP40 (modular enclosure) ratings per IEC 60529. Specific RoHS, REACH, or UL declarations are available from Schneider Electric upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Z22463","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Z22463 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}