{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9Z24291","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9Z24291","canonicalUrl":"https://aoctrl.com/schneider/A9Z24291","factsUrl":"https://aoctrl.com/api/mcp/products/A9Z24291","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iID, RCCB, 2P, 100 A, 300 mA, Type A, 220-240 V AC, DIN rail, IP20.","salesMarkdown":"## RCCB for panel builders — what the ratings mean Type A means it catches both sinusoidal AC faults and pulsating DC faults from electronics, so it covers modern loads like VFDs, UPS systems, and LED drivers. The A9Z24291 carries a rated conditional short-circuit current of 10 kA and a rated breaking and making capacity of 1500 A. The 10 kA figure is the maximum prospective short-circuit current it can withstand when backed by an upstream overcurrent device (MCB or fuse) of the appropriate rating — it is not a standalone breaking capacity. In practice this means it is suitable for installation at the load side of a distribution board where the fault level does not exceed 10 kA. The impulse withstand voltage is 6 kV, which covers transient overvoltages in standard AC networks. Pollution degree 3 confirms it is rated for the conductive-pollution environment typical of control panels and switchgear enclosures. ## Installation and wiring Clip-on mounting on DIN rail, neutral on the left. Terminals accept double front or back entry: up to 35 mm² rigid front, 25 mm² flexible front with ferrule, and 16 mm² flexible back. Wire stripping length is 14 mm for top or bottom connection. The toggle control has a contact position indicator and can be padlocked. IP20 body protection is standard for enclosed panels; the modular enclosure achieves IP40 when installed in a suitable cabinet.","metaTitle":"Schneider Electric A9Z24291 Acti9 iID RCCB, 100 A, 300 mA, T","metaDescription":"Schneider Electric A9Z24291 Acti9 iID RCCB, 100 A rated, 300 mA sensitivity, Type A, 2P, DIN rail mount, EN/IEC 61008-1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 61008-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iID","Mounting mode":"Clip-on","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Device short name":"iID","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"100 A","Electrical durability":"AC-1: 10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Earth-leakage sensitivity":"300 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 1500 A Im 1500 A","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"6 kV","Rated conditional short-circuit current":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9Z24291/acti-9-iid-rccb-2p-100a-300ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9Z24291/alternatives.json"},"ai":{"faq":[{"question":"What is the rated current and earth leakage sensitivity of A9Z24291?","answer":"The A9Z24291 is rated at 100 A with a 300 mA earth leakage sensitivity, Type A protection, per EN/IEC 61008-1."},{"question":"What compliance standards does A9Z24291 meet?","answer":"It is designed to EN/IEC 61008-1 for residual current circuit breakers. The rated impulse withstand voltage is 6 kV, and the electromagnetic compatibility includes 8/20 µs impulse withstand at 250 A to the same standard."},{"question":"Where can I buy A9Z24291 and how is it quoted?","answer":"The A9Z24291 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9Z24291","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9Z24291 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}