{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ACS510-01-246A-4","brand":"ABB","brandSlug":"abb","productSlug":"ACS510-01-246A-4","canonicalUrl":"https://aoctrl.com/abb/ACS510-01-246A-4","factsUrl":"https://aoctrl.com/api/mcp/products/ACS510-01-246A-4","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS510-01-246A-4 standard drive, R6 frame, 245 A nominal with 13.5 kW continuous rating, paired with an NBRA-658C chopper and a SAFUR200F500 braking resistor at 2.7 Ohm selection.","salesMarkdown":"The ABB ACS510-01-246A-4 is a standard drive from the ACS510 line, populated as the R6 frame and rated 245 A nominal (I2N) for 13.5 kW continuous (Prated) operation. On the braking side, the drive ships with the NBRA-658C chopper matched to a SAFUR200F500 braking resistor, with a Ppeak of 198 kW and an Rsel of 2.7 Ohm — the resistor selection is the one that limits peak braking energy in this stack. ## Braking envelope and resistor selection Peak braking on this build is 198 kW (Ppeak) into a 2.7 Ohm resistor selection, which is the figure that defines how much regen energy the chopper can sink on a fast stop or a vertical-axis load — not the continuous kW rating. The continuous power figure of 13.5 kW is the motor-shaft rating, not the resistor dissipation figure; the SAFUR resistor is sized for short, high-peak duty and the chopper handles the gating. ## Output choke and motor cable reach The FOCH-0260-70 output choke is rated at 289 A thermal current, giving headroom over the 245 A drive nominal when the motor cable run is long. Maximum motor cable length is 300 m with the choke and 300 m without it — for an R6 frame at this current that is a generous figure, but bear in mind the choke is what keeps the dV/dt at the motor terminals inside the insulation limit on those longer runs. ## Sourcing posture","metaTitle":"ABB ACS510-01-246A-4 drive, 245 A, R6, 13.5 kW cont.","metaDescription":"ABB ACS510-01-246A-4 standard drive, R6 frame, 245 A nominal with SAFUR200F500 braking resistor and NBRA-658C chopper; sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["AC Drives (VFD)"],"specifications":{"Rtype":"SAFUR200F500","title":"Standard Drivers","Weight":"73 Kg","Chopper":"NBRA-658C","Frame Size":"R6","Ppeak [kW]":"198","Rsel [Ohm]":"2.7","Product No.":"ACS510-01-246A-4","description":"Standard Drivers","Product Type":"ABB Standard Drives","Shipping Weight":"78 Kg","lifecycle_stage":"eol_hot","Estimated Lead Time":"Usually ships in 1-10 working days.","Prated (cont.) [kW]":"13.5","Nominal current I2N A":"245","Dimensions (L x W x H)":"40cm x 30.2cm x 98.6cm","Output choke type code":"FOCH-0260-70","Choke thermal current I A":"289","Max. cable length with choke m":"300","Max. cable length without choke m":"300"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$6,392.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/661ff3f79b07d12fd2ea92307e8d5806.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the listed Rtype on this ABB line?","answer":"The Rtype carried in the record is SAFUR200F500, paired with an NBRA-658C chopper and a 2.7 Ohm resistor selection."},{"question":"What is the continuous and peak power rating?","answer":"Continuous (Prated) is 13.5 kW and peak braking (Ppeak) is 198 kW into a 2.7 Ohm resistor selection."},{"question":"What is the maximum motor cable length with the output choke?","answer":"300 m with the FOCH-0260-70 output choke fitted, and 300 m without it."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/ACS510-01-246A-4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/ACS510-01-246A-4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}