{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"AF26-30-00-41","brand":"ABB","brandSlug":"abb","productSlug":"AF26-30-00-41","canonicalUrl":"https://aoctrl.com/abb/AF26-30-00-41","factsUrl":"https://aoctrl.com/api/mcp/products/AF26-30-00-41","rawCanonicalId":null},"summary":{"shortDescription":"ABB AF-Line Series, AF26 Frame, IEC Contactor, 45 Amp, 3-Pole, 600V Rated, 60 VAC/VDC Coil, AF26-30-00-41.","salesMarkdown":"The ABB AF26-30-00-41 is a 3-pole IEC contactor on the AF26 frame, rated for 45 A continuous current and a 600 V maximum insulation voltage. The 45 A rating is the AC-1 thermal current (Ith) — the continuous resistive load it can carry without derating. For motor duty (AC-3), the actual switching current will be lower, typically around 18–22 A for a standard 3-phase induction motor, so size the contactor to the motor full-load amps, not the 45 A headline figure. The coil is 60 VAC/VDC, which means it pulls in on either supply type at that nominal voltage; the pickup threshold is typically around 48 V and dropout below 18 V, so verify your control voltage stays above the pickup minimum during brownout conditions. ## Deployment context — panel integration In a control panel, this contactor occupies roughly 45 mm of rail width. The 3-pole power terminals accept up to 16 mm² cable; the coil terminals are spring-cage for 0.2–2.5 mm².","metaTitle":"AF26-30-00-41 ABB Contactor, 45 A, 3-Pole, 60 V Coil","metaDescription":"ABB AF26-30-00-41 IEC contactor, 45 A rated, 3-pole, 60 VAC/VDC coil. Current production. Sourced to order against RFQ. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Amps":"45","Type":"Contactor","Poles":"3","title":"AF26-30-00-41","description":"Contactor IEC, 60 VAC/VDC|45 Amp, 3-Pole, 600V Rated, 60 VAC/VDC Coil. AF-Line Series, AF26 Frame, IEC Contactor. *** Does not include Standard Aux Contacts, 3 Pole Contactor Only ***","lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$167.28","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b8c641aa25d271c2b1597e0e11022c4a.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the 45 A rating for on this contactor?","answer":"The 45 A is the AC-1 thermal current (Ith) — the continuous resistive load it can carry. For motor switching (AC-3 duty), the practical current is lower, typically 18–22 A for a 3-phase motor. Match the contactor to the motor full-load amps, not the 45 A headline."},{"question":"Where can I buy AF26-30-00-41?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/AF26-30-00-41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/AF26-30-00-41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}