{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"AH08DA-5B","brand":"Delta","brandSlug":"delta","productSlug":"AH08DA-5B","canonicalUrl":"https://aoctrl.com/delta/AH08DA-5B","factsUrl":"https://aoctrl.com/api/mcp/products/AH08DA-5B","rawCanonicalId":null},"summary":{"shortDescription":"Delta AH08DA-5B Analog Output Module, 8 points, 16-bit resolution, 150 µs/channel conversion, voltage ranges 0/1V~5V / ±5V / 0V~10V / ±10V.","salesMarkdown":"The Delta AH08DA-5B is an 8-channel analog output module that takes voltage signals from your PLC and converts them to real-world control levels. It handles 0/1V–5V, ±5V, 0V–10V, and ±10V ranges, so you can match it to drives, valve positioners, or chart recorders without extra signal conditioners. Each channel converts in 150 µs, which keeps the loop fast enough for most process and motion applications. The 16-bit hardware resolution gives you 65,536 steps across the full voltage span — at 0–10 V that's about 0.15 mV per step, which is fine for precision setpoints. Base error at ambient temperature is ±0.02% of full scale in voltage mode, ±0.06% in current mode; over the full temperature range it drifts to ±0.04% and ±0.07% respectively. Linearity error stays at ±0.004% regardless of temperature, so the module won't introduce a bend in your control curve. Power draw is split: 0.25 W from the backplane (internal) and 2.2 W from an external supply. That external draw matters if you're sizing a 24 VDC bus — 2.2 W is about 92 mA, so a bank of these modules adds up. The JIS removable terminal block makes wiring swaps easy without pulling the module off the backplane.","metaTitle":"AH08DA-5B Analog Output Module, 8 Points, 16-Bit, 150 µs/ch","metaDescription":"AH08DA-5B analog output module with 8 channels, 16-bit resolution, 150 µs/ch conversion. Supports 0/1–5V, ±5V, 0–10V, ±10V signals. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Analog Output Modules"],"specifications":{"Model":"AH08DA-5B","Points":"8","Signals":"0/1V~5V, ±5V, 0V~10V, ±10V","Manufacturer":"DELTA","Conversion time":"150 Âµs/channel","Shipping Weight":"2 Kg","lifecycle_stage":"current","Estimated Lead Time":"Usually ships in 1 - 10 working days.","Hardware resolution":"16-bit","Terminal block type":"JIS removable terminal block","Base error (ambient temp.)":"Voltage mode ±0.02% Current mode ±0.06%","Base error (full temp. range)":"Voltage mode ±0.04% Current mode ±0.07%","Linearity error (ambient temp.)":"Voltage mode ±0.004% Current mode ±0.01%","Linearity error (full temp. range)":"Voltage mode ±0.004% Current mode ±0.01%","Powerconsumption (Internal /External)":"0.25w / 2.2w"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$757.00","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/AH08DA-5B/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for AH08DA-5B?","answer":"It has 8 output points, 16-bit hardware resolution, conversion time of 150 µs per channel, and supports voltage ranges of 0/1V–5V, ±5V, 0V–10V, and ±10V. Base error at ambient is ±0.02% (voltage) / ±0.06% (current); linearity error is ±0.004% across temperature."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/delta/AH08DA-5B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/delta/AH08DA-5B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}