{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"APM1A0C20S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"APM1A0C20S6","canonicalUrl":"https://aoctrl.com/schneider/APM1A0C20S6","factsUrl":"https://aoctrl.com/api/mcp/products/APM1A0C20S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process Modular, power module, APM1A0C20S6, 200 HP at 600 V, 215 A continuous output, obsolete.","salesMarkdown":"Continuous output current is 215 A at 2.5 kHz switching frequency for normal duty, derating to 175 A for heavy duty. That gives you 1.1x current boost for 60 s under normal duty, 1.5x for heavy duty — enough for demanding starts but not for continuous overload. The switching frequency is adjustable from 2.5 to 4.9 kHz with a derating factor; lower frequencies mean less heat in the module but more audible noise on the motor. Apparent power runs 179 kVA normal duty, 158 kVA heavy duty at 600 V — useful for sizing upstream transformer. THDI is under 48% from 80-100% load, which meets most plant harmonic limits but check your site-specific requirement.","metaTitle":"Schneider APM1A0C20S6 Power Module, 200HP, Obsolete","metaDescription":"Obsolete APM1A0C20S6 Altivar Process Modular power module. 200 HP, 600 V, 215 A continuous output. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Depth":"510 mm","Width":"230 mm","Height":"1705 mm","Marking":"CE","Standards":"UL 61800-5-1 IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated with 300 m conforming to IEC 61800-3 category C3","Maximum THDI":"<48 % from 80...100 % of load","Mounting mode":"Cabinet mount","Apparent power":"179 kVA at 600 V normal duty 158 kVA at 600 V heavy duty","Motor power hp":"200 hp at 600 V normal duty 175 hp at 600 V heavy duty","Kit composition":"1 power module 1 mains unit 1 power supply for fan 48 V 1 relay for fan 3 fuse holder 2 brackets with nuts screws and washers for fuse","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process Modular","Shock resistance":"4 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"APM","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Operating altitude":"<= 4800 m with current derating above 1000m","Operating position":"Vertical integrated in cabinet","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz with derating factor 2.5...4.9 kHz adjustable","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Prospective line Isc":"50 kA","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Insulation resistance":"> 1 MOhm 500 V DC for 1 minute to earth","IP degree of protection":"IP00 conforming to IEC 61800-5-1 IP21 (for cabinet integration) conforming to IEC 61800-5-1 IP54 (for cabinet integration) conforming to IEC 61800-5-1","Network number of phases":"3 phases","Continuous output current":"215 A at 2.5 kHz for normal duty 175 A at 2.5 kHz for heavy duty","Product or component type":"Power module","[Us] rated supply voltage":"600 V - 15...10 %","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air temperature for storage":"-40...70 °C","Permissible temporary current boost":"1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)","Ambient air temperature for operation":"-10...40 °C (without derating) 40...50 °C (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/APM1A0C20S6/standard-power-module-altivar-process-modular-200hp-600v-ip00/","alternativesUrl":"https://aoctrl.com/api/mcp/products/APM1A0C20S6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/APM1A0C20S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/APM1A0C20S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}