{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"APM1L0C28Y6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"APM1L0C28Y6","canonicalUrl":"https://aoctrl.com/schneider/APM1L0C28Y6","factsUrl":"https://aoctrl.com/api/mcp/products/APM1L0C28Y6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Altivar Process Modular APM1L0C28Y6 power module, 280 kW normal duty, 500-690 V, liquid cooled, IP00, 308 A continuous output at 2.5 kHz.","salesMarkdown":"The Schneider APM1L0C28Y6 is a liquid-cooled power module from the Altivar Process Modular family, rated for 280 kW normal duty or 220 kW heavy duty at 500-690 V. It delivers 308 A continuous in normal duty at 2.5 kHz switching, 240 A in heavy duty. That's the number you feed your cable and breaker sizing calc. Designed for synchronous and asynchronous motors—think pumps, fans, conveyors where you need the density of liquid cooling in a cabinet. IP00 from the factory, but with cabinet integration you can hit IP21 or IP66 depending on the enclosure. No built-in EMC filter (category C3), so plan for an external filter if you need to meet Class A emission limits in a residential environment. Per the manufacturer, this is an active catalog item. The order code APM1L0C28Y6 is the full standard power module with no options. Expect standard lead times for an active Altivar Process Modular variant. ## Installation constraints Cabinet-mount, vertical only. Dimensions are 1018 mm high, 232 mm wide, 526 mm deep. That 526 mm depth means you need a cabinet at least 600 mm deep for cable bends and airflow. Liquid cooling circuit required—no fan cooling. Operating range is 5-55 °C coolant temp, ambient -10 to 40 °C without derating, up to 50 °C with derating. Altitude derating above 1000 m. Pollution degree 2 environment, 50 kA prospective short-circuit current rating withstand. Vibration per IEC 60068-2-6: 1.5 mm pp at 2-13 Hz, 0.5 gn at 13-200 Hz. Shock 4 gn for 11 ms. Keep that in mind for offshore or mobile installations. CE marked. Standards suite includes UL 61800-5-1, IEC 61800-3 (EMC for adjustable-speed drives), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic currents), IEC 60721-3 (environmental classification), IEC 61508 and IEC 13849-1 (functional safety). EMC immunity test levels 3 or 4 per IEC 61000-4-2 through -4-6. This covers most industrial installations. No RoHS or REACH declaration data in our record, but Schneider typically provides it on request.","metaTitle":"Schneider APM1L0C28Y6 Power Module, 280 kW, 500-690V, Liquid","metaDescription":"Active Altivar Process Modular power module, 280 kW/300 hp, 500-690V, 308 A normal duty, IP00, liquid cooled. Standards: UL 61800-5-1, IEC 61800-3. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Depth":"526 mm","Width":"232 mm","Height":"1018 mm","Marking":"CE","Standards":"UL 61800-5-1 IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Without EMC filter conforming to IEC 61800-3 category C3","Maximum THDI":"<9 % full load at 12-pulse supply","Mounting mode":"Cabinet mount","Apparent power":"243 kVA at 500 V normal duty 199 kVA at 500 V heavy duty 271 kVA at 600 V normal duty 191 kVA at 600 V heavy duty 347 kVA at 690 V normal duty 282 kVA at 690 V heavy duty","Motor power hp":"300 hp at 600 V normal duty 200 hp at 600 V heavy duty","Motor power kW":"280 kW at 500...690 V (normal duty) 220 kW at 500...690 V (heavy duty)","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process Modular","Shock resistance":"4 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Operating altitude":"<= 4800 m with current derating above 1000m","Operating position":"Vertical integrated in cabinet","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Prospective line Isc":"50 kA","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Insulation resistance":"> 1 MOhm 500 V DC for 1 minute to earth","IP degree of protection":"IP00 conforming to IEC 61800-5-1 IP21 (for cabinet integration) conforming to IEC 61800-5-1 IP66 (for cabinet integration) conforming to IEC 61800-5-1","Network number of phases":"3 phases","Continuous output current":"308 A at 2.5 kHz for normal duty 240 A at 2.5 kHz for heavy duty","Product or component type":"Power module","[Us] rated supply voltage":"500...690 V - 10...10 %","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Coolant temperature for operation":"5...55 °C","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-10...40 °C (without derating) 40...50 °C (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/APM1L0C28Y6/standard-power-module-altivar-process-modular-280-kw-500690v-ip00-liquid-cooled/","alternativesUrl":"https://aoctrl.com/api/mcp/products/APM1L0C28Y6/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings for APM1L0C28Y6?","answer":"Normal duty: 280 kW, 308 A continuous at 2.5 kHz. Heavy duty: 220 kW, 240 A. Supply voltage 500-690 V."},{"question":"What compliance standards does this module meet?","answer":"CE marked. Complies with UL 61800-5-1, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/APM1L0C28Y6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/APM1L0C28Y6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}