{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"APM1L0C31N4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"APM1L0C31N4","canonicalUrl":"https://aoctrl.com/schneider/APM1L0C31N4","factsUrl":"https://aoctrl.com/api/mcp/products/APM1L0C31N4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Altivar Process Modular power module, APM1L0C31N4, 315 kW, 380-480 V, 590 A ND, IP00, liquid-cooled.","salesMarkdown":"The Schneider APM1L0C31N4 is a power module from the Altivar Process Modular line, delivering 590 A continuous at 2.5 kHz for normal duty, 477 A for heavy duty, on a 380-480 V three-phase supply. Rated 315 kW normal duty for asynchronous or synchronous motors. Liquid-cooled for dense cabinet builds; cabinet mount only, vertical position. No internal EMC filter — expecting C3 environment or external filtering. ## Mounting & cabling Cabinet footprint: 1018 mm high, 232 mm wide, 526 mm deep. IP00 chassis; IP21 or IP66 achievable with proper cabinet integration. Operating altitude up to 4800 m with current derate above 1000 m. Ambient operating range -10 to 40 °C without derating; 40-50 °C with derate. Coolant supply temperature 5-55 °C. Pollution degree 2, suitable for controlled industrial environments. ## Compliance & lifecycle EMC immunity meets EN/IEC level 3 for ESD, radiated RF, and conducted disturbance; level 4 for fast burst. THDI under 9 % at full load with 12-pulse supply. ## Sourcing Active, factory-current. Match the continuous output current (590 A ND / 477 A HD) and motor power (315 kW ND) to your drive specification. Quoted to order; submit an RFQ for lead time and pricing.","metaTitle":"Schneider APM1L0C31N4 Power Module, 590A ND","metaDescription":"Active-production Altivar Process Modular power module, 315 kW / 590 A ND at 380-480V, liquid-cooled, IP00. CE, UL 61800-5-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"526 mm","Width":"232 mm","Height":"1018 mm","Marking":"CE","Standards":"UL 61800-5-1 IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Without EMC filter conforming to IEC 61800-3 category C3","Maximum THDI":"<9 % full load at 12-pulse supply","Mounting mode":"Cabinet mount","Apparent power":"371 kVA at 400 V normal duty 297 kVA at 400 V heavy duty 373 kVA at 440 V normal duty 300 kVA at 440 V heavy duty 438 kVA at 480 V normal duty 353 kVA at 480 V heavy duty","Motor power hp":"500 hp at 480 V normal duty 400 hp at 480 V heavy duty","Motor power kW":"315 kW at 380...480 V (normal duty) 250 kW at 380...480 V (heavy duty)","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process Modular","Shock resistance":"4 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Operating altitude":"<= 4800 m with current derating above 1000m","Operating position":"Vertical integrated in cabinet","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Prospective line Isc":"50 kA","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Insulation resistance":"> 1 MOhm 500 V DC for 1 minute to earth","IP degree of protection":"IP00 conforming to IEC 61800-5-1 IP21 (for cabinet integration) conforming to IEC 61800-5-1 IP66 (for cabinet integration) conforming to IEC 61800-5-1","Network number of phases":"3 phases","Continuous output current":"590 A at 2.5 kHz for normal duty 477 A at 2.5 kHz for heavy duty","Product or component type":"Power module","[Us] rated supply voltage":"380...480 V - 10...10 %","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Coolant temperature for operation":"5...55 °C","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-10...40 °C (without derating) 40...50 °C (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/APM1L0C31N4/standard-power-module-altivar-process-modular-315-kw-380480v-ip00-liquid-cooled/","alternativesUrl":"https://aoctrl.com/api/mcp/products/APM1L0C31N4/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does it carry?","answer":"CE marking, and listed standards include UL 61800-5-1, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/APM1L0C31N4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/APM1L0C31N4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}