{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"APM9A0CTLN401","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"APM9A0CTLN401","canonicalUrl":"https://aoctrl.com/schneider/APM9A0CTLN401","factsUrl":"https://aoctrl.com/api/mcp/products/APM9A0CTLN401","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process Modular control module, APM9A0CTLN401, 380-480 V, STO SIL 3, Modbus serial and Ethernet Modbus TCP.","salesMarkdown":"## Control module for the Altivar Process drive family The APM9A0CTLN401 is the control module for the Altivar Process Modular drive series, rated for a 380-480 V supply. It carries STO (safe torque off) certified to SIL 3, which means the drive can be safely disabled without removing power — critical for integration into safety circuits that need a controlled stop. Communication is handled over Modbus serial (RS-485, 2-wire) and Ethernet Modbus TCP, with the RJ45 ports on the remote graphic terminal included in the kit. ## Supply rails and wiring Three separate supply rails feed this module: 24 V DC (19-30 V) for the digital inputs, a regulated 10.5 V DC ±5 % for an external reference potentiometer (1-10 kOhm), and a dedicated 24 V DC (21-27 V) rail for the digital inputs and STO logic. The insulation test is 1 MOhm at 500 V DC for one minute to earth. Keep the STO supply separate from the main control supply if you need galvanic isolation for the safety loop. ## Environmental and EMC profile Rated for operation at -10 to 40 °C without derating, and up to 50 °C with derating. Pollution degree 2 per IEC 61800-5-1. EMC immunity meets level 3 for electrostatic discharge, radiated RF, conducted RF, and surge (1.2/50 µs - 8/20 µs), and level 4 for fast transients. The module is IP00 — intended for enclosure mounting where the cabinet provides the environmental seal.","metaTitle":"Schneider APM9A0CTLN401 Altivar Process control module, 380-","metaDescription":"Active APM9A0CTLN401 Altivar Process control module, 380-480 V, STO SIL 3, Modbus serial/Ethernet. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Frequency":"50...60 Hz - 5...5 %","IP Rating":"IP00","Product Status":"Active","Pollution Degree":"2 conforming to IEC 61800-5-1","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"50 °C","Temp Operating Min":"-10 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Control module"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aaa74b1cf6c0efcd3a299c7fe6ca14ac.pdf","sourceUrl":"https://www.se.com/nl/en/product/APM9A0CTLN401/standard-atv900-control-unit-apm-single-drive-380480v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/APM9A0CTLN401/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/APM9A0CTLN401","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/APM9A0CTLN401 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}